ID 442426.04
336
WE KEEP THINGS MOVING
Optimize
15
Manual SD6
15.1.3.4
Current controller
Clock frequency of the drive controller power board.
Increasing the clock frequency improves the control dynamics and reduces the
amount of noise produced, but also leads to increased losses (derating of the
power stage
R04
,
R26
).
In some operating states the clock frequency is changed by the drive controller
itself. The currently active clock frequency is displayed in
E151
.
Action time of the current controller for the torque/ force-generating part in ms.
A setting below 0.3 ms will result in an integral gain of 0 (equivalent to an infinite
action time).
Proportional gain of the torque/ force controller.
Action time of the current controller for the flow generating part in ms. A setting
below 0.3 ms will result in an integral gain of 0 (equivalent to an infinite action
time).
B24
switching frequency
version 2
E165
E92
PID controller
B64 B65 B68
E98
PWM
B24
M
E166
E93
PID controller
B66 B67 B68
E99
Information
The factory setting of this parameter depends on
B20
. If a
synchronous servo motor or synchronous linear motor is used, the
value
8:8kHz
is entered in
B24
. If an asynchronous machine is
used,
B24
has a value of
4:4kHz
.
4: 4 kHz
8: 8 kHz
16: 16 kHz
17: 4 + 8 kHz automatic
18: 8 + 16 kHz automatic
19: 4 + 8 + 16 kHz automatic
B64
integral time torque/force controller
version 0
B65
proportional gain torque/force controller
version 0
B66
integral time Id
version 0