6 | Technical data
STOBER
38
02/2019 | ID 442728.05
6
Technical data
Technical data for the drive controllers, supply modules and accessories can be found in the
following chapters.
6.1
General technical data
The following specifications apply equally to the SI6 drive controller and the PS6 supply module.
Device features
Protection class of the device
IP20
Protection class of the installation
space
At least IP54
Radio interference suppression
Integrated line filter in accordance with EN 61800-3:2012,
interference emission class C3
Overvoltage category
III in accordance with EN 61800-5-1:2008
Test symbols
Tab. 11: Device features
Transport and storage conditions
Storage/
transport temperature
−20 °C to +70 °C
Maximum change: 20 K/h
Relative humidity
Maximum relative humidity 85%, non-condensing
Vibration (transport) in accordance
with DIN EN 60068-2-6
5 Hz ≤ f ≤ 9 Hz: 3.5 mm
9 Hz ≤ f ≤ 200 Hz: 10 m/s²
200 Hz ≤ f ≤ 500 Hz: 15 m/s²
Tab. 12: Transport and storage conditions
Operating conditions
Surrounding temperature during
operation
0 °C to 45 °C with nominal data
45 °C to 55 °C with derating −2.5% / K
Relative humidity
Maximum relative humidity 85%, non-condensing
Installation altitude
0 m to 1000 m above sea level without restrictions
1000 m to 2000 m above sea level with −1.5%/100 m derating
Pollution degree
Pollution degree 2 in accordance with EN 50178
Ventilation
Installed fan
Vibration (operation) in accordance
with DIN EN 60068-2-6
5 Hz ≤ f ≤ 9 Hz: 0.35 mm
9 Hz ≤ f ≤ 200 Hz: 1 m/s²
Tab. 13: Operating conditions
Discharge times
Self-discharge of DC link
15 min
DC link circuit fast discharge
Thanks to PS6 supply module in combination with a braking
resistor:
< 1 min
Tab. 14: Discharge times of the DC link circuit