13.3.11 Event 40: Invalid data
The drive controller is interrupted:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an
inactive release override (F06)
Number
Cause
Check and action
1: Fault
–
8: Wrong/illegal serial number
Invalid data in the internal
memory of the drive controller
or option module
Replace the drive controller or option
module; fault cannot be acknowledged
32: Electronic nameplate
No data available in the
electronic nameplate
Deactivate the evaluation of the
nameplate or replace the motor (B04);
fault cannot be acknowledged
33: Electronic motor-type limit
Invalid data in the electronic
nameplate
Deactivate the evaluation of the
nameplate or replace the motor (B04);
fault cannot be acknowledged
48: reverse documentation
Defective memory in the SD
card or internal memory of
the drive controller
Replace the SD card or drive controller;
fault cannot be acknowledged
Tab. 194: Event 40 – Causes and actions