STI LATCHING/TIMER MODEL LT-1UL

NOTE

It is important to read, understand and follow all instructions provided with this product. It is the installer’s responsibility to 

comply with NFPA 70, 72 & 101, NEC, mounting specifications according to ADA and other applicable codes. This product 

is not to be used in place of panic hardware. To avoid electrical shock, DO NOT attempt to install this product when power 

is on. After installation and testing are complete, provide a copy of this manual to all personnel responsible for testing and 

maintenance of this product. 

*For access control installations, power for the LT-1UL Timer must be supplied by a power source Listed to UL294. When 

used for access control, this device shall be used a part of an access controlled egress door system. It is up to the local AHJ 

to allow use of this device in place of an automatic sensor. For higher security installations, lower time limits should be used.

RELAY MODE

N.O. - Relay N.O. -switches with power to circuit - Fail Secure (default)

N.C. - Relay is in same state as with no power to circuit - Fail Safe (cut jumper)

TO CHANGE TIMER SETTINGS (default = 15 seconds): Cut jumpers with “X”, do not cut jumpers with “        “.

  

If the trigger is activated during a timing cycle, the timer is restarted.

NOTE

 To ensure jumpers do not reattach or short to other components, cut jumper off completely flush to PCB.

+

-

+

-

x

RELAY ACTIVE LED RED

POWER LED GREEN

1.28 in.

33mm

1.74 in.

44mm

.632 in.

16mm

#6 - 32 x 5/16”

PHILLIPS PAN HEAD SCREW

(2) PROVIDED

 

CASE BASE 

CASE TOP

LT-1PCB

 

POWER IN

12 - 24 VAC/VDC

TIMER

CONTROL

FORM “C”

DRY CONTACTS

3A, 30VDC

RESET

INPUT COM

TRIGGER

N.C.

COM

N.O.

TIMER START

SWITCH

TIMER OVERRIDE

RESET (OPTIONAL)

*POWER IN

12-24 VAC/VDC

TO MAGNETIC LOCK

(FAIL SAFE MODE)

JUMPERS

15 SEC

RELAY MODE JUMPER

30 SEC 45 SEC LATCH

+

-

*POWER IN

≠≠VAC/VDC, 18 mA

TIMER

CONTROL

FORM “C”

DRY CONTACTS

3A, 30VDC

RESET

INPUT COM

TRIGGER

N.C.

COM

N.O.

19082 #6 - 32 x 5/16”

PHILLIPS PAN HEAD SCREW

(2) PROVIDED

 

CASE BASE 

LT-1PCB

 

CASE TOP

FAIL SAFE MODE

WIRING DIAGRAM

FAIL SECURE MODE

WIRING DIAGRAM

12-24 VAC/VDC

12-24 VAC/VDC

UB-1/UB-2

UB-1/UB-2

BUTTON LED

CONTACT SET 1

CONTACT SET 2

MESSAGE LED

BUTTON LED

CONTACT SET 1

CONTACT SET 2

MESSAGE LED

NO COM

NO

NC

NC

COM

NO COM

NO

NC

NC

COM

+

RST

INPUT COM

TRIG

RELAY NC

RELAY COM

RELAY NO

+

RST

INPUT COM

TRIG

RELAY NC

RELAY COM

RELAY NO

LT-1

LT-1

DOOR

LOCK

RESET SWITCH

(OPTIONAL EXCEPT ON

LATCH TIMER SETTING)

DOOR

LOCK

RESET SWITCH

(OPTIONAL EXCEPT ON

LATCH TIMER SETTING)

ILLUMINATING GREEN

ILLUMINATING RED

SHOWN: POWER ON

NORMAL CONDITION

x x

x

ELECTRONIC INSULATION PAPER

 

IF TRACES ARE INADVERTENTLY CUT,

SOLDER JUMPER WIRES USING

APPROPRIATE HOLES.

RELAY MODE

N.O.

N.C.

NO CUT

CUT

15s

30s

45s

Ltch

Relay

NO

Relay

COM

Relay

NC

Trig

Input

Com

Reset

Power

Input

+

-

12 to 24 Volts

AC or DC

MODEL LT-1

RELAY MODE

N.O.

N.C.

NO CUT

CUT

15s

30s

45s

Ltch

+

-

+

-

x

RELAY ACTIVE LED RED

POWER LED GREEN

1.28 in.

33mm

1.74 in.

44mm

.632 in.

16mm

#6 - 32 x 5/16”

PHILLIPS PAN HEAD SCREW

(2) PROVIDED

 

CASE BASE 

CASE TOP

LT-1PCB

 

POWER IN

12 - 24 VAC/VDC

TIMER

CONTROL

FORM “C”

DRY CONTACTS

3A, 30VDC

RESET

INPUT COM

TRIGGER

N.C.

COM

N.O.

TIMER START

SWITCH

TIMER OVERRIDE

RESET (OPTIONAL)

*POWER IN

12-24 VAC/VDC

TO MAGNETIC LOCK

(FAIL SAFE MODE)

JUMPERS

15 SEC

RELAY MODE JUMPER

30 SEC 45 SEC LATCH

+

-

*POWER IN

≠≠VAC/VDC, 18 mA

TIMER

CONTROL

FORM “C”

DRY CONTACTS

3A, 30VDC

RESET

INPUT COM

TRIGGER

N.C.

COM

N.O.

19082 #6 - 32 x 5/16”

PHILLIPS PAN HEAD SCREW

(2) PROVIDED

 

CASE BASE 

LT-1PCB

 

CASE TOP

FAIL SAFE MODE

WIRING DIAGRAM

FAIL SECURE MODE

WIRING DIAGRAM

12-24 VAC/VDC

12-24 VAC/VDC

UB-1/UB-2

UB-1/UB-2

BUTTON LED

CONTACT SET 1

CONTACT SET 2

MESSAGE LED

BUTTON LED

CONTACT SET 1

CONTACT SET 2

MESSAGE LED

NO COM

NO

NC

NC

COM

NO COM

NO

NC

NC

COM

+

RST

INPUT COM

TRIG

RELAY NC

RELAY COM

RELAY NO

+

RST

INPUT COM

TRIG

RELAY NC

RELAY COM

RELAY NO

LT-1

LT-1

DOOR

LOCK

RESET SWITCH

(OPTIONAL EXCEPT ON

LATCH TIMER SETTING)

DOOR

LOCK

RESET SWITCH

(OPTIONAL EXCEPT ON

LATCH TIMER SETTING)

ILLUMINATING GREEN

ILLUMINATING RED

SHOWN: POWER ON

NORMAL CONDITION

x x

x

ELECTRONIC INSULATION PAPER

 

IF TRACES ARE INADVERTENTLY CUT,

SOLDER JUMPER WIRES USING

APPROPRIATE HOLES.

RELAY MODE

N.O.

N.C.

NO CUT

CUT

15s

30s

45s

Ltch

Relay

NO

Relay

COM

Relay

NC

Trig

Input

Com

Reset

Power

Input

+

-

12 to 24 Volts

AC or DC

MODEL LT-1

RELAY MODE

N.O.

N.C.

NO CUT

CUT

15s

30s

45s

Ltch

+

-

x

TIMER START

SWITCH

TIMER OVERRIDE

RESET (OPTIONAL)

*POWER IN

12-24 VAC/VDC

TO MAGNETIC LOCK

(FAIL  SECURE MODE)

JUMPERS

15 SEC

RELAY MODE JUMPER

30 SEC 45 SEC LATCH

ILLUMINATING GREEN

ILLUMINATING RED

x x

x

SHOWN: POWER ON

NORMAL CONDITION