1
CMCP700S-CVT Series
User Manual
Ver. 1.1
Released July 27, 2021
Страница 1: ...1 CMCP700S CVT Series User Manual Ver 1 1 Released July 27 2021...
Страница 2: ...Engineering Unit Selection 4 Full Scale Range Settings 4 Low Pass Filter Settings 5 Temperature Output 5 Buffered Output 5 Sensor Fault Detection 5 4 20mA Outputs 5 Wiring 5 Terminal Pin Assignments...
Страница 3: ...Power The CMCP700S Series Transmitters require externally supplied DC power The power supply should have a nominal output of 24VDC and be capable of supplying a minimum of 100mA for each CMCP700S Seri...
Страница 4: ...witches R1 R2 or R3 The Full Scale Range controls the 4 20mA output scaling To determine the Full Scale range choose the sensor type in the left hand column and match it to the range setting The facto...
Страница 5: ...r OK Fault Indicator The CMCP700S CVT features a local sensor status LED on the front panel The LED is controlled by the transmitters OK circuitry When the transmitter is powered on and the sensor is...
Страница 6: ...ower 2 VIB Sensor Input Common 3 TEMP IN Temperature Input 10mV C Buffered Output 4 BUF VIB Buffered Dynamic Output Signal 5 COM Buffered Output Common Analog Outputs 8 COM Common 9 4 20 OUT TEMP 4 20...
Страница 7: ...ield adjustments or service Transmitters are designed to provide years of continuous trouble free service under normal operating conditions To obtain a return materials authorization number please con...
Страница 8: ...8 Revision History Revision Release Date Updates 1 0 July 2 2021 Manual Release 1 1 July 27 2021 OK fault detection circuit...