RF Rx SW868/915/917/922-NET-4S-A
Montage- und Anschlussanleitung / Funk-Aktor
Mounting and wiring instructions / Wireless actuator
Instructions de montage et de câblage / Actionneur sans fil
Istruzioni di montaggio e collegamento / Attuatore wireless
Instruções de montagem e instalação / Atuador sem fio
Инструкция по монтажу и подключению / Радио-привод
st
eut
e T
echnol
ogies GmbH & Co. K
G
Brück
ens
tr
aße 91, 32584 Löhne, Germany
, www
.s
teut
e.c
om
2 / 16
Deutsch (Originalbetriebsanleitung)
Entsorgung
- Nationale, lokale und gesetzliche Bestimmungen zur Entsorgung
beachten.
- Materialien getrennt dem Recycling zuführen. Eventuell enthaltene
Batterien fachgerecht entsorgen.
English
Intended use
The device of type SW868 is intended for use(in the European Union. It
complies with the European Union’s Directive 2014/53/EU (RED) for
radio equipment.
The device of type SW915 is intended for use in Canada, USA, and Mex-
ico. It complies with the requirements of FCC Rules and IC Rules, RSS-
210. It has an approval number for the Mexican states.
The device of type SW917 is intended for use in Brazil. It complies with
the requirements of Resolucão 242/2000.
The device of type SW922 is intended for use in Japan. It complies with
the requirements of ARIB STD-T108.
The four-channel wireless actuator is used to switch electrical loads
via radio transmission. The transmission is carried out at a frequency
of 868.3, 915, 917 or 916,5 MHz. The receiver must conform to the
sWave.NET
r
protocol of the steute modules.
Mounting and wiring
Mount the device on an even surface. The wireless range depends on
the local conditions. Thus, the radio signal can be strongly affected by
conductive materials. This also includes thin foils, e.g. aluminium lam-
inations on insulation materials.
Use suitable antennas only. Antenna with cable and SMA plug-in con-
nector, Mat. No. 1188958 (SW868/922) or 1188987 (SW915/917). Mount
the antenna on a metal plate. The metal plate serves as HF counter-
weight. Minimum size of metal plate: 250 x 250 mm. Observe mini-
mum sideways distance to nearest wall or disturbance source:
>300 mm. Do not bend or clamp the cable.
Minimum bending range of cable: >25 mm.
Design of wireless range
Because radio signals are electromagnetic waves, the signal is attenu-
ated on its way from the transmitter to the receiver. This means the
electrical as well as the magnetic field strengths decrease inversely
proportional to the squared distance of transmitter and receiver
(E,H~1/r²). In addition to this natural restriction of the wireless range,
further interference factors occur: Metal parts, e. g. armours in walls,
metal foils of thermal insulations or vapour deposited metal layer heat
protection glass, reflect electromagnetic waves. Therefore, a so-called
deadspot can be found behind them. Radio waves are able to penetrate
walls, but the attenuation increases even more than in the free field.
Penetration of radio waves:
wood, gypsum, glas uncoated
90...100%
brick stone, press boards
65...95%
armoured concrete
10...90%
metal, aluminium lamination, water
0...10%
Typical wireless ranges are:
Outdoor range (SW868/915/917):
approx. 450 m
Outdoor range (SW922):
approx. 150 m
Indoor range (SW868/915/917):
approx. 40 m
Indoor range (SW922):
approx. 20 m
Max. range in free field (SW868/915/917)
approx. 700 m
Max. range in free field (SW922)
approx. 230 m
Max. range indoors (SW868/915/917)
approx. 50 m
Max. range indoors (SW922)
approx. 25 m
To reach the maximum range: use the specified antennas. With other
antennas, the maximum range may differ.
Start-up and select operation mode
Requirements:
- Mount device on standard DIN rail.
- Connect cable for supply voltage 24 VDC.
- The LEDs show the operating states. If the wireless actuator and the
green MD LED MD are both switched on, then the device is ready
for use.
Switching the relays
Switching the relays:
Set the relays as described in the »Description of
interface« in paragraph »RECORD.RELAIS.SWITCH« (see RF RxT
SW868/915/917/922-NET, »Description of interface«, section »Data-
Message«, download from www.steute.com). The relays are always
switched during wakeup time of RF Rx SW868/915/917/922-NET-4S-A.
Set wakeup time:
Set wakeup time as described in the »Description of
interface« in paragraph »RECORD.WAKEUP« (see RF RxT
SW868/915/917/922-NET, »Description of interface«, section »Data-
Message«, download from www. steute.com).
For example: »0x01« for relays switching once a minute.
Safety
Do not use the device in connection with other devices whose direct or
indirect purpose is to ensure life or health, or whose operation may
pose a threat to humans, animals or material assets. The described
products were developed in order to assume safety functions as part of
an entire plant or machine. It is the responsibility of the manufacturer
of a plant or machine to guarantee the correct general function.
N.B.
We reserve the right to make design changes in line with technological
progress. Reconstruction and alterations at the device are not allowed.
steute does not assume any liability for recommendations made or im-
plied by this description. New claims for guarantee, warranty or liabili-
ty cannot be derived from this document beyond the general terms and
conditions of delivery.