Technical Data Sheet

9100 ThermElect Hydronic

Models 9150 and 9180

2-Year Limited Manufacturer’s Warranty

Steffes | 3050 Highway 22 North | Dickinson, North Dakota 58601-9413 | 701-483-5400 

Rev 3

Clearances and Dimensions

Storage Module (53kW and 80kW)

• 

Back = 8 inches

• 

Bottom = 1 inch (from combustible material)

• 

Right Side = 12 inches

• 

Top = 8 inches (from combustible material)

• 

Left Side & Front = 36 inches (for ease in servicing)

Adhere to clearances and provide appropriate 

ventilation to maintain no greater than 85

o

F air 

temperature in area where unit is installed.

Some electrical codes may require a greater 

front clearance depending on operating 

voltages and other factors.

Placement

The minimum area required for the installation of the system is 100 square feet per unit. This area must remain free of 
debris and room air should be maintained at less than 85

o

 Fahrenheit / 29

o

 Celsius.  It is the responsibility of the installer 

and system designer to provide appropriate ventilation to control temperature in area where unit is placed.

IMAGE #:

REV:

1201158

0

51"

9180 - 98"
9150 - 77"

40 

1

16

"

80KW

STORAGE

MODULE

34"

12" MINIMUM

CLEARANCE

8" MINIMUM

CLEARANCE

36" MINIMUM

CLEARANCE

36" MINIMUM

CLEARANCE

12" MINIMUM

CLEARANCE

8" MINIMUM

CLEARANCE

36" MINIMUM

CLEARANCE

IMAGE #:

REV:

1201159

0

1"

CLEARANCE

REQUIRED