STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 34
9.1.6. Alarm Levels
Alarm level 1 is associated with Relay 1, setting between 1 and 100% FSD
Alarm level 2 is associated with Relay 2, setting between 1 and 100% FSD
Alarm level 3 is associated with Relay 3, setting between -1 and -10% FSD
•
From the menu system select menu option:
Alarm Levels
and
press ENTER.
Alarms
Select
Level:
1 2 3
•
Using the
button to select the desired alarm level and press
ENTER. The Edit window will appear
Alarms
Edit
.
+
•
Use the
button to select an individual digit or the + sign the use
the
button to change the + to a
– and the digit to 0 through 9,
continue for all digits until the desired alarm s
et point is set.
•
Press ENTER to accept the new alarm level,
will be
displayed
Note: Pressing MENU instead of ENTER leaves the alarm set
point unchanged.
•
Press MENU to return the instrument to the Alarms level select
menu option.
•
Use the Using the
button to select the next desired alarm
level and press ENTER.
•
Press the MENU button to exit the alarms option menu. On exit
the display will show
f no changes have been made
or if changes have been made.
Updated
No change
Data updated