5.2.20
C: 46
– Response window
This option is used in conjunction with the averaging values. This option is available so
that the FGD3 can be set for optimum response time.
The value can be increased to obtain a quicker response to gas at the expense of
decreasing the gas readings stability.
Note:
changing this value from the factory setting may make the readings
unstable
– consult Status Scientific Controls Ltd before making any
changes.
•
Press MENU to open the menu system.
•
Using the NEXT and PREVIOUS buttons, select menu option:
C:46
•
Press ENTER.
•
Using the INCREASE and DECREASE buttons, set the required
averaging value.
•
Press ENTER to store the new value.
Note: Pressing the MENU button rather than the ENTER button exits
without any change.
•
Press MENU to close the menu system.