13

Observe interior through opening - a small flashlight may be used
effectively.

If the interior still shows water scale, the deliming process should
be continued.

To check UN•LIME®  for continued use or reuse, place some lime
scale or white chalk into a glass with a small amount of the solution.
If the material is vigorously dissolved by the solution, the UN•LIME®
can be reused. If not, then UN•LIME®  has been weakened and
should be replaced.

DELIMING THE GPO WATER HEATER

FIGURE 18

8. When deliming has been completed, the heater should be flushed for

3 to 5 minutes with fresh water.

Remove the deliming equipment, install the drain valve, open the
cold water inlet line and allow water to flow through heater and out
the drain valve.  Don't forget to plug vent and cap opening in Flo-
Jug.

9. When flushing is completed:

Fill heater being certain to expel air from tank through a nearby hot
water faucet.

Replace relief valve, removed for deliming.

Restore oil, water and electrical supply to heater.

Check for water leakage.

10.Flo-Jug Cleanup.

Allow  scale to separate from UN•LIME®  and settle on bottom
of Flo-Jug.

Pour off UN•LIME®  into plastic container and check for reuse.

Rinse sediment from Flo-Jug.

If UN•LIME®  is reusable , pour back into Flo-Jug. Be sure to plug
vent and cap opening.

CIRCULATING PUMP

The water heater or water heating system may include a circulating pump.
Where used, it may need to be lubricated once every four months with
SAE No. 20 non-detergent motor oil or as directed by the manufacturer.

Place 2 or 3 teaspoons in the bearing oil cup and 10 to 12 drops in the
motor oil cups.

SOOT REMOVAL

Soot must be removed semi-annually from the heater and flow passages
to insure efficient operation of the heater.

                    

A TYPICAL HEATER FLUEWAY AND FLUE BAFFLE

FIGURE 19

1. Remove chimney connector and top cover of heater from heater.  Clean

out all soot deposits from connector and chimney opening.  A wire
brush is recommended for this operation.

2. Remove flue baffles by lifting from tank.

3. Using a wire brush, remove soot from flue passages in heater tank.

CAUTION: While cleaning tank flue passages, care must be taken that

brush does not come in contact with the top of the combustion
chamber as damage could occur to the combustion chamber
lining.

4. Remove oil burner assembly and using a vacuum cleaner, remove all

loose soot from combustion chamber area.  Avoid contact with
combustion chamber as it can be damaged quite easily.

If flange gasket is damaged, replace with State Part No. 24165

5. Upon completion of cleaning, reassemble the heater.  (It may be

necessary to apply new sealer tape to the top cover to ensure proper
venting.  New sealer tape can be ordered from State Water Heaters).

6. Return the heater to operation by following the start-up instructions

on page 10.

VENT SYSTEM

Examine the vent system every six months for obstructions and/or
deterioration of vent piping. Remove any soot or obstructions and replace
damaged vent piping.

ANODE ROD INSPECTION

The anode rod is used to protect the tank from corrosion. Most hot water
tanks are equipped with an anode rod. The submerged rod sacrifices
itself to protect the tank. Instead of corroding the tank, water ions attack
and eat away the anode rod. This does not effect the water's taste or
color. The rod must be maintained to keep the tank in operating condition.

Anode rod deterioration depends on water conductivity, not necessarily
water condition. A corroded or pitted anode rod indicates high water
conductivity and should be checked and/or replaced more often than an
anode rod that appears to be intact. Replacement of a depleted anode
rod can extend the life of your water heater. Inspection should be conducted
by a qualified technician, and at a minimum should be checked annually
after the warranty period.

Содержание GPO 69-700(A)

Страница 1: ... 000 COMMERCIAL OIL FIRED WATER HEATER FOR HOT WATER SUPPLY Installation Operation Service Maintenance MODELS GPO 86 199 THRU GPO 69 700 A CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOUROUGHLY BEFORE USING APPLIANCE 500 Lindahl Parkway Ashland City TN 37015 www stateind com ...

Страница 2: ...50 2357 2063 1833 1650 1500 1375 1269 1179 GPO 700 000 69 80 GPH 1677 1341 1118 958 838 745 671 610 559 516 479 69 700 A 205 261 LPH 6347 5077 4231 3627 3173 2821 2539 2308 2116 1953 1813 ALL DIMENSIONS IN INCHES mm Model numbers followed by the suffix A indicates the optional A S M E tank construction TABLE 1 NOMINAL MODEL DIMENSIONS GPO 86 199 GPO 86 245 GPO 84 315 A GPO 75 385 A GPO 75 455 A GP...

Страница 3: ...ted by Underwriters Laboratories Inc Accordingly the burner bears one of the UL labels indicating periodic inspection of the production of this equipment All ASME tanks are built to the standards of Section IV of the American Society of Mechanical Engineers code and are stamped with their symbol The National Board of Boiler and Pressure Vessel Inspectors papers are furnished upon request The NB nu...

Страница 4: ...UIT If it is necessary to reset the safety primary control depress red button one time only If burner does not operate after depressing red button one time call serviceman INSTALLATION REQUIRED ABILITY INSTALLATION OF SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENCED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING OIL BURNER AND ELECTRICAL WORK REQUIRED GEN...

Страница 5: ...ng approved provisions must be made to overcome the problem see NFPA Standard No 31 Chapter 1 CHEMICAL VAPOR CORROSION Water heater corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calcium and sodium chlorides waxes and process chemica...

Страница 6: ... supplied with a flue reducer which should be installed on the top cover In venting systems where a continuous or intermittent back positive draft is found to exist the cause must be determined and corrected In some cases a special vent cap may be required If the back draft cannot be corrected by normal methods or if a suitable draft cannot be obtained a blower type flue gas exhauster must be empl...

Страница 7: ...burner shutoff system actuated by high water temperature CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in the cold water line between the water heater and the street main or well Excessive pressure may develope due to the thermal expansion of heated water causing premature tank failure or intermitten...

Страница 8: ...0 30 4 7 2 1 31 9 4 100 30 4 3 0 9 50 15 2 100 30 4 8 2 4 26 7 9 100 30 4 4 1 2 45 13 7 100 30 4 9 2 7 21 6 4 83 25 2 5 1 5 40 12 1 100 30 4 10 3 0 16 4 8 64 19 5 Two Stage Supply and Return Lines This system fig 12 is required when long lines and high lifts requiring up to 20 of vacuum and 10 vertical lift are encountered Burner Series No 941 is used in this service Bypass plug must be installed ...

Страница 9: ...eater or water system 3 All burners have intermittent ignition as defined by UL ignition is on during the time the burner is on and off when the burner is off 4 Do not test fire the heater to complete the oil burner certificate until the tank is filled with water see the oil burner manual The certificate and this manual must be left with the user for future reference TABLE 8 OIL PUMP NOZZLE SPECIF...

Страница 10: ...NJURY OCCURS VARIES WITH THE PERSONS AGE AND TIME OF EXPOSURE THE SLOWER RESPONSE TIME OF CHILDREN AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP OR TO DRAW THEIR OWN BATH WATER NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS...

Страница 11: ...l Annually Anode Semi Tank Inspection Annually Lime Scale As UN LIME Removal Required Delimer Circulating Four SAE No 20 non detergent Pump Oiling Months motor oil Inspection Combustion test and Semi kit test specifications Oil Burner Adjustment Annually Page 26 Nozzle Semi Replacement Annually New Nozzle Flue Baffle Pipe Cleaning Annually Wire Brush Venting Semi System Inspected Annually RELIEF V...

Страница 12: ...nt using care not to damage the glass lining 5 Inspect cleanout plate gasket If new gasket is required replace with State Part no 99038 6 Install cleanout plate Be sure to draw plate up tight by tightening screws securely 7 Fill the water heater according to the FILLING section on Page 10 8 Check for water leakage 9 Replace outer jacket cover plate Flo jug Method of Deliming The Flo Jug is the sta...

Страница 13: ... connector and top cover of heater from heater Clean out all soot deposits from connector and chimney opening A wire brush is recommended for this operation 2 Remove flue baffles by lifting from tank 3 Using a wire brush remove soot from flue passages in heater tank CAUTION While cleaning tank flue passages care must be taken that brush does not come in contact with the top of the combustion chamb...

Страница 14: ...ATION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES NOTE WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 19 mm OPENING FOR TAN...

Страница 15: ...E TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES WIRING DIAGRAM FOR 180 F 82 2 C LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER SUPPLY LINE IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY INSET B VACUUM R...

Страница 16: ...FE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES WIRING DIAGRAM FOR 180 F 82 2 C LOOP IF USED INSTALL IN ACCORDANCE WITH LOCAL CODES WIRING DIAGRAM FOR TEMPERED WATER LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER S...

Страница 17: ...E TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSET B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER SUPPLY LINE IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY WIRING DI...

Страница 18: ...ROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP CONTROL SHOULD BE SET AT 185 F 85 C NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK NOTE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A WIRING DIAGRAM FOR 180 LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WA...

Страница 19: ...nits with the higher water flow may have a shortened life Unions and T P valves shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by complete assemblies Service space in front of units must be added DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEA...

Страница 20: ... the most common cause of relief valve leakage It is often caused by a closed system If a check valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the water heater or plumbing system will be damaged When such a condition is encountered local codes or inspection agency should be consulted to de...

Страница 21: ...ust be reset before trying again for ignition When this occurs allow about 5 minutes for safety heater to cool before depressing the red safety button Depress red button one time only If burner does not operate after depressing red button one time check combustion chamber If combustion chamber is soaked with oil the combustion chamber must be replaced Some of the possible reasons for flame failure...

Страница 22: ...nting screws slightly and shift Noisy fuel pump in different positions until noise is eliminated Operation Retighten mounting screws Air in inlet line Check all connections Use only good flare fittings Tank turn on two line pipe system and inside tank Install return line hum eliminator Partially clogged strainer or filter Remove and clean strainer Air leak in intake line Tighten all fittings Air l...

Страница 23: ... GPO XX 199 245 315 385 455 700 AND GPO XX 315A 385A 455A 700A ITEM NO 13 ITEM NO 25 REPLACEMENT PARTS LIST CLEANOUT ASSEMBLY OIL STATE WATER HEATERS 500 Lindahl Parkway Ashland City TN 37015 Phone 800 821 2017 Fax 800 644 9306 www stateind com ...

Страница 24: ...5 192495 192495 192495 Hot 192484 192484 192484 192484 192484 192484 Relief Valve 191068 191068 191068 191068 191068 191068 UL 193657 193657 1 193657 2 193657 3 193657 4 193657 5 Inlet 94518 94518 94518 94518 94518 94518 Outlet 94519 94519 94519 94519 94519 94519 Wiring Diagram 193694 193694 193694 193695 193695 193695 17 Gasket Skirt Ring 76443 76443 76443 76443 76443 76443 18 Insulation Foil Fac...

Отзывы: