Temperature transmitter Ex i
Series 9182
9
Parameterization and Commissioning
Before commissioning, ensure the following:
• Installation of the device according to regulations.
• Correct connection of the cables.
• No damage at the device and connection cables.
• Tight seat of the screws at the terminals.
Correct tightening torque: 0.5 to 0.6 Nm.
9.1
Replacement of the Device
• If replacing this with a device that has an identical design, readjust the DIP switch and
parameterise it using ISpac Wizard, if necessary.
9.2
Parameterizations
9.2.1 User Adjustment of the Operating Modes
All operating modes can be adjusted using the ISpac Wizard 9199 software.
The variants (9182/a0-5d-11 a=1.2; d=1.9) can also be adjusted using the DIP switch.
The temperature transmitter Type 9182 must be parameterised according to the
application using:
• the lateral DIP switch "S2" or
• the ISpac Wizard software
Lateral 12-pole DIP switch
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
The user adjustment through software can be carried out once all lateral
DIP switches have been set to "OFF."
Modification of the 12-pole DIP switch "S2" (lateral) during operation will not
become effective until after a short interruption of the auxiliary power supply
(PWR-ON Reset)!