CPU & power module
for Zone 2/Class I, Div. 2
Series 9440/15
8.2
Mounting / Dismounting, Operating Position
8.2.1 Mounting / Dismounting on BusRail
12228E00
Mounting on BusRail
NOTICE
Malfunction or device damage caused by improper mounting.
Non-compliance may lead to material damage!
• Mount the device in vertical direction only, with the reading direction of the
LCD display from below, left or right, as desired.
22319E00
• Position the module vertically at the
first slot of the BusRail and press
lightly to snap it into place.
• Press the module down onto the
BusRail on the left and right to ensure
that it is properly secured!
There should not be any gap between
the module and BusRail!
The module must not be able to
disconnect without the notch lever
being actuated.
• Plug the pluggable terminal X5 into
the module and secure it against
loosening using safety screws
(tightening torque 0.5 to 0.6 Nm).
BusRail
BusRail