Compact Luminaire with LED
Series C-Lux 6102/1, Series C-Lux 6109/1
6.2
Installation
6.2.1 Electrical connections
Mains connection
Observe the following when connecting to the mains connection:
Clamping must be carried out precisely!
Do not clamp any part of the conductor insulation!
Do not mix up the conductors.
Observe the technical regulations when connecting the conductor.
Clamp the conductor firmly.
Connection terminals
Observe the maximum clamping possibility of the connection terminals
(see chapter "Technical data").
Clamping range:
1 x 1.5 to 4 mm
2
finely stranded
1 x 1.5 to 6 mm
2
solid or finely stranded with core end sleeve
(2 free clamping units per pole available)
Stripping length:
10 to 12 mm
Standard (series 6102/1):
20219E00
L1, L2, L3
= phase
N
= neutral conductor
PE
= protective conductor
with DALI connection (series 6102/1):
20221E00
D1, D2
= DALI connection
L1, L2, L3
= phase
N
= neutral conductor
PE
= protective conductor
L3
L2
L1
N
PE
L3
L2
L1
N
PE
D1
D2