Commissioning
9
Empty Enclosure
Series 8150/0
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
6.2
Installation
6.2.1 Protective Conductor Connection
In general, consider the following when connecting a protective conductor:
Always connect the protective conductor.
Use cable lugs for external protective conductor connection.
Permanently install the protective conductor close to the enclosure.
Connect all uncoated, non-energised metal parts to the protective conductor system.
Neutral conductors have to be installed as live conductors.
7
Commissioning
Before commissioning, carry out the following checks:
Check the enclosure for damage.
Make sure that all openings/drilled holes in the enclosure are sealed with permissible
components. Dust and transport protection (adhesive tape or plastic caps) provided
at the factory must be replaced with appropriately certified components.
Make sure that seals and sealing systems are clean and undamaged.
Remove any foreign bodies.
Check whether all the specified tightening torques have been observed.
8
Maintenance, Overhaul, Repair
Comply with the applicable national standards and regulations in the country of use,
e.g. IEC/EN 60079-14, IEC/EN 60079-17, IEC/EN 60079-19.
8.1
Maintenance
Check the following points in addition to the national regulations:
• Whether the device enclosure and/or protective enclosure has cracks or other visible
signs of damage
• Check for compliance with the permitted temperatures.
• Whether the parts are securely fastened
8.2
Overhaul
Perform maintenance on the device according to the applicable national regulations
and the safety notes in these operating instructions ("Safety" section).
8.3
Repair
Perform repairs to the device only using original spare parts and after consulting with
R. STAHL.
Operation under difficult conditions, such as on ships or in strong sunlight, requires
additional measures to be taken to ensure that the device is installed correctly,
depending on the operating location. Further information and instructions on this can
be obtained from your regional sales contact upon request.
DANGER! Risk of explosion due to improper installation!
Non-compliance may result in serious or even fatal injury.
Install the device carefully and only in accordance with the safety notes
("Safety" chapter).
The installation steps stated below must be carried out very precisely.