133285 / 8118609300
2019-11-13·BA00·III·en·06
Product Selection, Project Engineering and Modification
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Terminal Boxes
Series 8118/1, Series 8118/2
All dimensions in mm [inches]
18105E00
When punching and cutting, make sure that the outer surfaces of the enclosure
remain flat and undamaged (without cracks).
Observe the mounting clearances when creating the drilled holes.
Adjust the hole diameters to the dimensions of the built-in parts or their seals.
ONLY use built-in components with flat seal (gasket).
Observe Chapter 5.2 when subsequently equipping components!
If the technical data has changed, e.g. due to the components that are to be additionally
installed, attach the new rating plate with the current values.
5.2
External Attached Components
(Cable Entries, Stopping Plugs, Breathers)
5.2.1 Fitting of Attached Components by R. STAHL
Give the following information to R. STAHL:
- Type
- Data sheet
- Quantity, manufacturers and approvals of the components that are to be attached.
- Type of protection
R. STAHL
• will check whether the components, quantity and position correspond with the approval
• will mount the components
• will update the order documentation
• will carry out a routine test
• will, if necessary, fit a new type plate if the technical data has changed,
e.g. due to the components that are to be additionally attached.
Drilled holes are generally fitted with the components intended for the application at the
factory.
If customers intend to fit the components in the holes themselves, dust and transport
protection is provided for the openings in the enclosure (adhesive tape with a warning
note or plastic caps) at the factory.