Appendix A
18
290163 / 949660310110
2021-08-05·BA00·III·en·00
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Socket for CPU and power modules
for Zone 1
Series 9496/32
13
Appendix A
13.1 Technical Data
Explosion protection
Global (IECEx)
Gas
IECEx PTB 17.0026X
Ex ia IIC T4 Gb
Europe (ATEX)
Gas
PTB 17 ATEX 2010 X
E
II 2 G Ex ia IIC T4 Gb
Certificates and approvals
Certificates
IECEx, ATEX, EAC (Eurasian Economic Union), NEPSI
Ship certificates
EU RO Mutual Recognition (in preparation)
(incl. ABS, BV, CCS, CRS, DNV GL, IRS, KR, LR, ClassNK, PRS, RINA, RS)
Further parameters
Installation in
Zone 1 and safe area
Further information
See operating instructions and certificates
Technical data
Electrical data
Slots
Number of slots
3 or 4
(for IS1+ Remote I/O CPU module 9442/32 and power module 9445/32)
Configuration for
redundant power
supply
1 x 9442/32 CPU and 2 x 9445/32 power module
Configuration for
redundant
communication
2 x 9442/32 CPU and 1 x 9445/32 power module
Configuration for
system
redundancy
2 x 9442/32 CPU and 2 x 9445/32 power module
Power supply
via power module(s) 9445/32
Max. power
consumption
125 W
Max. power
dissipation
0.5 W
Communication
with I/O modules
Via BusRail 9494
Electromagnetic
compatibility
Tested to the following standards and regulations:
EN 61326-1 (2013) IEC 61000-4-1 to 61000-4-6, NAMUR NE 21