Load and motor switch/
control switch
Series 8006/4
14
Appendix A
14.1 Technical Data
Explosion protection
Global (IECEx)
Gas
IECEx PTB 06.0018U
Ex db eb ia IIC Gb
Ex db eb ia I Mb
Europe (ATEX)
Gas
PTB 01 ATEX 1021 U
E
II 2 G Ex db eb ia IIC Gb
E
I M 2 Ex db eb ia I Mb
Certifications and certificates
Certifications
IECEx, ATEX
Technical data
Electrical data
Rated insulation
voltage
Max. 690 V AC
Rated frequency
50/60 Hz
Rated operational
voltage
max. 690 V AC/220 V DC (load and motor switch);
250 V DC (control switch)
min. 24 V AC/DC (recommendation for contact safety)
Rated impulse
withstand voltage
6 kV
Rated operational
current
max. 32 A
min. 100 mA
(Recommended for contact safety: Min. one switching per week)
Contacts
max. 12-pole/6 switching levels
*)
*)
The switches have two contact chambers per switching level.
Freely assembling individual switching levels, each equipped with one or
two contact paths, to form one functional unit enables optimal adaptation to
the application. The contact chambers are actuated by separate control gears
so that switching over 360° can be performed with no mutual interference.
Switching capacity
as per IEC/EN 60947
-
3; IEC/EN 60947
-
4
-
1; IEC/EN 60947
-
5
-
1:
AC
-
3
AC
-
15
AC
-
23
DC
-
1, DC
-
23 DC
-
13
(L/R = 300 ms)
690 V, 25 A
400 V, 10 A
690 V, 25 A
220 V, 25 A
3)
250 V, 1.1 A
1)
500 V, 32 A
120 V, 25 A
2)
125 V, 2.2 A
1)
60 V, 25 A
1)
60 V, 5.0 A
1)
1)
1 conducting path
2)
2 conducting paths in series
3)
3 conducting paths in series