Commissioning
8
8040606300
S-BA-8040-en-02-15/06/2007
Control and signal station
8040
The only exception to this is the use of cables in which the cores of the intrinsically safe
or the non-intrinsically safe circuit are surrounded by an earthed screen.
The pre-conditions for the separation between parts to be connected for
intrinsically safe and non-intrinsically safe circuits are:
X
a distance of 50 mm around an insulating (
)
1 mm thick) or earthed metal
(
)
0.45 mm thick) isolating plate or
X
an isolating plate which is separated from enclosure walls by a distance of
(
1.5 mm.
9
Commissioning
Before commissioning, ensure that:
X
the control station has been installed according to the directions
X
the control station is not damaged
X
there are no foreign bodies inside the control station
X
connections have been made correctly
X
the cables have been made correctly
X
all screws and nuts are fully tightened
X
the cable glands and stopping plugs are securely tightened
X
unused cable entries are sealed with plugs certified to Directive 94/9/EC, and unused
holes are sealed by stopping plugs certified to Directive 94/9/EC.
WARNING
Please convince yourself before operation that the enclosure is completely without
damage.
WARNING
Excessive tightening of cable glands and stopping plugs can impair the degree of
protection.
)
We recommend the use of type 8290 stopping plugs for unused holes and
type 8161 stopping plugs for unused cable entries. Both are available from
Fa. R. STAHL Schaltgeräte GmbH.
Содержание 130665
Страница 1: ...Betriebsanleitung Operating Instructions Befehls und Meldeger t Control and signal station 8040...
Страница 2: ......
Страница 3: ...Betriebsanleitung Befehls und Meldeger t 8040...
Страница 14: ......
Страница 15: ...Operating Instructions Control and signal station 8040...
Страница 26: ......
Страница 30: ......
Страница 31: ......
Страница 32: ...8040606300 S BA 8040 de en 02 15 06 2007...