WWW.SSTCOMM.COM
9
Pin
Function
1
TXD, RS-232 data sending, Connect RXD of user device
2
RXD, RS-232 data receiving, Connect TXD of user device
3
GND
2.3.3 Serial II-RS485
Pin
Function
1
D+, RS485 Data Positive, connect Data Positive of user device
2
D-, RS485 Data Negative, connect Data Negative of user device
3
GND
2.3.4 Standard RS485 Characteristics
The basic characteristics of RS485 transmission technology:
Network topology: Linear bus, there are active bus terminal resistors at both sides.
Transmission rate: 1200 bps~115.2Kbps.
Media: Shielded twisted-pair cable and also can cancel the shielding, depending on environmental
conditions (EMC).
Site number: 32 stations per subsection (without repeater), and can increase up to 127 stations (with
repeater). When serial port 1 and serial port 2 simultaneously connect the slave equipment as the Modbus
master or User config, serial port 2 can configure up to 3 nodes. When configuring serial port 2 as the
Modbus master independently, it can configure up to 4 nodes.
Plug connection: 5-pin pluggable terminal.
The main points on the installation of RS485 transmission equipment:
All the equipment are connected with RS485 bus;
The farthest two end of the bus has a terminal resistor—120Ω 1/2W to ensure reliable operation of the
network.
Serial interface uses 5-pin pluggable open terminal and user can wire it according to the wiring instructions
D+
D-
GND
Содержание GT200-PN-RS