5 Working Principle
Inside the gateway it opens up a length of 5000 bytes of memory as the data exchange of input and output
buffers. Memory of 0 to 2999 acts as the storage area of the HART input data and device status. Memory of 3000
to 4999 acts as storage area of the HART output data and control variables. The specific assignment shown in the
table below:
Gateway
memory
address
Corresponding
Modbus register
address
Description
R
ea
d-o
nly
pa
rt
0-1599
0-799
The HART data input area
1600-1619
800-809
Device 0_cmd0 data
1620-1639
810-819
Device 1_cmd0 data
……
……
……Device 15_cmd0 data
1920
960H
Gateway status
1921
960L
Send times of Gateway’s HART port
1922
961H
Receive times of Gateway’s HART port
1923
961L
HART communication error times
1924-1943
962-971
Reserved
1944
972H
Device 0_cmd0’s response status
1945
972L
Device 1_cmd0’s response status
……
……
……Device15 _cmd0’s response status
1960-2119
980-1059
The response status of the user command
2120-2391
1060-1195
Reserved
2392
1196H
Universal receive label
2393
1196L
Universal receive Error Counter
2394-2395
1197
Universal receive data length
2396-2695
1198-1347
Universal receive data
2696-2999
Reserved
R
ea
da
ble
an
d
w
rita
ble
pa
rt
3000-3999
0000-0499
The HART data output area
4000
0500H
Reset to send, receive, error counter
Содержание GT200-HT-RS
Страница 10: ...WWW SSTCOMM COM 10...
Страница 17: ...WWW SSTCOMM COM 17 3 5 Topology of GT200 HT RS and Fieldbus Devices...
Страница 43: ...WWW SSTCOMM COM 43 After clicking Upload data it will show uploading succeeded...
Страница 44: ...WWW SSTCOMM COM 44...
Страница 52: ...WWW SSTCOMM COM 52 Installing the gateway Uninstalling the gateway...