User Manual
3-channel HART/Modbus TCP Gateway
GT200-3HT-MT
WWW.SSTCOMM.COM
8
Note: In HART protocol, it specifies that the device with slave address 0 works under single point mode, it allows
digital communication and analog communication exist simultaneously. The device with slave address 1~15
works under the multipoint mode, the analog output of the device is the minimum value and it only allows digital
communication. The protocol also specifies that the fieldbus device default address is 0 before delivery.
7. Right click Channel1, select “Add Node” in the popup menu as below:
8. Right click: “Node(0)”, select “Add Command” in the popup menu, add Command ID1 in the popup dialog
box (double click “Command ID1” or select “Command ID1” and click “»”), click OK to return.
9. Click “Command ID1”, the configuration table on the right is configured as below: