DIGIVEX Motion - PROFIBUS
10
PVD 3554 GB 01/2004
2.3 Control and status words
The control and status words correspond to the specifications in PROVIdrive Profile V2.0 and/or
V3.0 for the “positioning” mode.
Assigning STW1 control word bits
STW1 control word (bits 0 - 11 as defined in the PROFIDrive Profile, bits 12 - 15 specific to
DIGIVEX Motion.
BIT VALUE
MEANING
COMMENTS
1
ON
Sets the drive to “ready to run” status
0
0
OFF 1 = ABORT
Stoppage
using
brakes:
movement
stops
(abort_cmd = 1) in accordance with programmed
acceleration (accel_prog) then set to zero torque
(torque_cmd = 0) when the axis is shutdown
(moving = 0)
This function is not active when the drive is in speed
drive mode (drive_mode = 1)
1 ON
Operating
condition
1
0
OFF2 = TORQUE CMD
Freewheel stoppage: motor set to zero torque
(torque_cmd = 0)
1 ON
Operating
condition
2
0
ARRET3
=
EMERGENCY
Fast stoppage (emergency_cmd = 1) fastest
possible deceleration (accel_max) then set to zero
torque (torque_cmd = 0) when moving = 0
1
Torque mode
Automatic drive control lifted (torque_cmd = 1):
motor torque set
3
0
Zero torque
Automatic control implemented: motor set to zero
torque (torque_cmd = 0)
1 ON
Operating
condition
4
0
EMERGENCY STOP
Fastest possible braking (emergency_cmd = 1). No
zero torque setting when the axis is shutdown
(different from STW1 bit 2)
1
MOVE EN
Movement is authorized (move_en = 1)
5
0
Movement stoppage
Movement in progress is suspended (move_en = 0).
Movement is stopped using programmed
deceleration (accel_prog)
6
-
-
Not in use
1
Acknowledge fault
Fault is acknowledged with a rising front (reset_cmd
= 1)
7
0
-
Normal operating condition
8
-
-
Not in use
9
-
-
Not in use
1
Control word validation
Drive follows control words from the Master
10
0
Invalid control words
Drive ignores control words from the Master
1
HOME
Origin setting sequence is running (home_cmd = 1)
11
0
-
Origin setting sequence is not running (home_cmd =
0)