This document covers the steps necessary 
for a basic start-up of the 650 drive.  Drive 
start ups should be performed by qualified 
electrical technicians who are familiar with 
AC drives and their applications. For de-
tailed installation and safety information 
refer to the Instruction Manual.  

Ensure that all local electric codes are met 
while installing the drive. Check that all live 
parts are covered to protect against electric 
shock and that unexpected rotation of the 
motor will not result in bodily harm or injury. 

This document expects that the drive is 
already installed in its intended location 
and that all relevant installation procedures 
have been followed. Please ensure that the 
drive has adequate ventilation so that am-
bient temperature does not exceed 40°C 
(104°F) under normal operating conditions. 

To access the terminals, slide down the 
terminal cover, while applying slight pres-
sure on the drive label. 

S

ER IA L

  C

OMMS

 

The 6513 Serial Communication option can be 
plugged into the keypad slot. It can be used to 
exchange information between the Master and 
Slave drives in RS485/232 format, up to 32 units 
can be connected together. Front panel LED in-

Single-phase supply to L1, L2/N. 

3-phase supply to L1, L2, L3. 

Motor connections to M1, M2, M3. 

Brake resistor between DC+, DBR 

NOTE

: Frame 1&2 

230V units are not 

fitted with a braking module. Do not use 
a braking resistor on them

Motor thermistor to Th1A, Th1B. 

Ground lugs are provided for each power 
circuit. Follow proper grounding and shield-
ing methods as described in the Instruction 
Manual. 
If  stop  time  is  expected  to  be  less  than  the 
natural coasting time of the load, connect 
the braking resistor across DC+ and DBR 
(see Brake resistor note above) 

The power terminals shown are for frame 2. 
Although other frames may vary slightly in 
appearance, their terminal designations and 

Volts/Hertz 

mode (650 & 650V) – Basic 

open loop operation, used in fans/pumps 
and multi-motor applications. 

Sensorless Vector

 mode (650V only) – 

Tight speed regulation with good transient 
torque capability, without the need for 
speed feedback.  

C

O NTRO L

 M

OD E S

 

F

RA M E

  R

AT INGS

 

Frame 1

       0.3 – 1 HP                230VAC   1 ph 

                      

0.25 – 0.75kW           

Frame 2

       1.5 – 2 HP                230VAC   1 ph 

                      

1.1 – 1.5kW             

 

                      0.5 – 3 HP                460VAC   3 ph 
                      

0.37 – 2.2kW            400VAC

 

Frame 3

       3 – 5 HP                   230VAC   3 ph 

                      

2.2 – 4kW                 400VAC 

                      5 – 10 HP                 460VAC   3 ph 
                      

3 - 7.5kW                  400VAC 

For larger sizes, see 650V Quickstart 

6 5 0

6 5 0

 series

 series

 

 

Q u i c k   S t a r t

Q u i c k   S t a r t

 

 

P

OW ER

 C

ON NE C T IONS

 

f r a m e s   1

f r a m e s   1

-

-

3

3

 

 

Volts/Hertz (model 650) 

Inverters 

Sensorless (model 650V) 

*HA470679U100*

 

C

LO NIN G

 

650 and 650V drives may be cloned using the 
6514 Clone option that plugs into the keypad 
slot. Settings include to/from, I/O configuration 
and full/part transfer. 

A

DVA NC ED

  F

EAT UR E S

 

The 650 has additional features which can be ac-
cessed via the drive menu, or for the 650V using 
CE_Lite. Refer to the product manual for details.

 

Flycatching 

- When enabled, lets the drive start 

into a spinning load by doing a frequency search. 

Skip Frequencies 

– Two selectable avoidance fre-

quencies and associated window for each.

 

PID

 – Provides closed loop process control

 

S-Ramp

 – When enabled, introduces a second 

order slope to the ramp for smoother transitions.

 

Configurable Outputs 

– The digital outputs on the 

650 can be configured to pick one of 6 parameters. 
The outputs on the 650V are totally configurable. 

Auto Restart 

- After a fault, the drive attempts a 

number of restarts after a settable delay. 

Custom Screens 

- Allows the use of a Custom pa-

rameter to be displayed. (650V only) 

Encoder 

– Terminals 12 &13 (650V only) can be 

used for a quadrature (not complementary) encoder 
input for steady-state speed feedback.  

thermistor

thermistor

braking

braking

resistor

resistor

~

~

motor

motor

AC Line Input

AC Line Input

thermistor

thermistor

braking

braking

resistor

resistor

~

~

motor

motor

AC Line Input

AC Line Input

AC Line Input

AC Line Input

Visit us at www.SSDdrives.com 

USA: (704) 588-3246      UK: +44 (0)1903 737000 

HA470679U100    Issue 2 

Отзывы: