All-in-one Solar Energy Storage Inverter Controller
2
5
“ENT” button to enter the parameter editing mode, and the value of the parameter is flashing.
Adjust the value of the parameter with the “UP” and “DOWN” buttons. Finally, press the “ENT”
button to complete the parameter editing and return to the parameter selection state.
Parameter
no.
Parameter
name
Settings
Description
00
Exit setting
menu
[00] ESC
Exit the setup menu
01
Output source
priority
[01] SOL
PV priority mode, switching to the Mains when
the PV fails or the battery is lower than the set
value of parameter [04].
[01] UTI
default
Mains priority mode, switching to inverter only
when the mains fails.
[01] SBU
Inverter priority mode, switching to the mains
only when the battery is under voltage or lower
than the set value of parameter [04].
02
Output
Frequency
[02] 50.0
Bypass self-adaptation; when the mains is
connected, it automatically adapts to the mains
frequency; when the mains is disconnected, the
output frequency can be set through this menu.
The default output frequency of the 230V
machine is 50HZ
。
[02] 60.0
03
AC Input
Voltage
Range
[03] APL
Wide mains input voltage range of 230V
machine: 90~280V
[03] UPS
default
Narrow mains input voltage range of 230V
machine: 170~280V
04
Battery Power
to Utility
Setpoint
[04] 46.0
default
When the parameter [01] =SOL/SBU, the
battery voltage is lower than the set value, and
the output is switched from the inverter to the
mains. Setting range: 44V~52V.
05
Utility to
Battery Power
Setpoint
[05]56.0V
default
When the parameter [01] =SOL/SBU, the
battery voltage is higher than the set value, and
the output is switched from the mains to the
inverter. Setting range: 48V~60V.