All-in-one solar charge inverter V4.0 1
All-in-one solar charger inverter
User Manual
Product models:
HFP4850S80-145 | HFP4835U80-145
Страница 1: ...All in one solar charge inverter V4 0 1 All in one solar charger inverter User Manual Product models HFP4850S80 145 HFP4835U80 145...
Страница 2: ...flammable or explosive or heavily dusty areas The mains input and AC output are high voltage so please do not touch the wiring terminals The housing of the all in one solar charge inverter is hot when...
Страница 3: ...EL CONNECTION IN SINGLE PHASE 19 2 4 4 SCHEMATIC DIAGRAM OF PARALLEL CONNECTION IN SPILIT PHASE 22 3 OPERATING MODES 33 3 1 CHARGING MODE 33 3 2 OUTPUT MODE 34 4 LCD SCREEN OPERATING INSTRUCTIONS 35 4...
Страница 4: ...ploys advanced SPWM technology and outputs pure sine wave to convert DC into AC It is ideal for AC loads such as household appliances power tools industrial equipment and electronic audio and video eq...
Страница 5: ...ut to power the load while charging the battery If the mains or generator is not connected the system can also operate normally and the load is powered by the battery and PV module 3 Battery Provided...
Страница 6: ...er switch Dry contact port AC input port Cooling fan AC output port Battery port Grounding screw hold Cooling fan RS485 2 communication port PV port Current sharing port parallel module only Touch the...
Страница 7: ...All in one solar charge inverter V4 0 7 1 4Dimension drawing...
Страница 8: ...have been tightened and the wires are secured with ties to avoid looseness of connections caused by shaking of wires during mobile application The system connection wires are selected according to a c...
Страница 9: ...ircuit currents of all PV modules connected in parallel the short circuit current of the PV array shall not exceed the maximum input current Refer to the table below for PV input wire diameter and swi...
Страница 10: ...d inverter AC output current Maximum bypass output current Recommended air switch or circuit breaker type HFP4850S80 145 10mm2 7AW G 22A 40A 2P 40A HFP4835U80 145 10mm2 7AW 30A 40A 2P 40A Note The wir...
Страница 11: ...n one solar charge inverter ensure that there is enough air flowing through the heat sink and space of at least 200m to the left and right air outlets of the inverter shall be left to ensure natural c...
Страница 12: ...nect the external circuit breaker and confirm that the wire used is thick enough Please refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection Properly connect the AC input wire acco...
Страница 13: ...ire first and then the live wire and the neutral wire The ground wire is connected to the grounding screw hole on the cabinet through the O type terminal Ground L Live N Neutral Note The grounding wir...
Страница 14: ...t negative pole BAT wiring method Prior to wiring disconnect the external circuit breaker and confirm that the wire used is thick enough Please refer to Section 2 2 Wiring Specifications and Circuit B...
Страница 15: ...ust be installed at the battery terminal Refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection to select a right circuit breaker Before wiring be sure to disconnect the circuit brea...
Страница 16: ...ains Finally turn on AC loads one by one as the AC output is normal to avoid a protection action caused by a large momentary shock due to simultaneous turning on the loads simultaneously Now the machi...
Страница 17: ...nnection is correct with the same wiring length and line diameter before power on and start up so as to avoid the abnormal operation of parallel system output caused by wrong connection 2 AC OUT wirin...
Страница 18: ...rent phases cannot be joined together Other connection precautions are the same as parallel connection in single phase For specific wiring please refer to 2 4 4 Wiring Diagram 4 Wiring of parallel com...
Страница 19: ...tions are the same as parallel connection in single phase For specific wiring please refer to 2 4 4 Wiring Diagram 6 Before or after connecting the system please carefully refer to the following syste...
Страница 20: ...All in one solar charge inverter V4 0 20 b Three all in one solar charger inverters of the system connected in parallel...
Страница 21: ...All in one solar charge inverter V4 0 21 c Four all in one solar charger inverters of the system connected in parallel d Five all in one solar charger inverters of the system connected in parallel...
Страница 22: ...parallel connection in spilit phase 1 The parallel communication line and current sharing detection line of the all in one solar charger inverter need to be locked with screws after connecting The sc...
Страница 23: ...allel Operation in two phase only for U series model can be set a Two all in one solar charger inverters of the system connected in two phase 1 1 system b Three all in one solar charger inverters of t...
Страница 24: ...All in one solar charge inverter V4 0 24 c Four all in one solar charger inverters of the system connected in two phase 2 2 system...
Страница 25: ...All in one solar charge inverter V4 0 25 3 1 system d Five all in one solar charger inverters of the system connected in two phase 4 1 system...
Страница 26: ...All in one solar charge inverter V4 0 26 3 2 system e Six all in one solar charger inverters of the system connected in two phase 5 1 system...
Страница 27: ...All in one solar charge inverter V4 0 27 4 2 system 3 3 system...
Страница 28: ...allel Operation in three phase for U and S series model a Three all in one solar charger inverters of the system connected in three phase 1 1 1 system b Four all in one solar charger inverters of the...
Страница 29: ...All in one solar charge inverter V4 0 29 c Five all in one solar charger inverters of the system connected in three phase 3 1 1 system...
Страница 30: ...All in one solar charge inverter V4 0 30 2 2 1 system d Six all in one solar charger inverters of the system connected in three phase 2 2 2 system...
Страница 31: ...efore starting up and running please check whether the connection was correct to avoid any abnormalities in the system 2 All wiring must be fixed and reliable to avoid wire drop during use 3 When the...
Страница 32: ...set to 2P2 the AC output line voltage difference is 180 degrees L1 L2 line voltage is 120 2 240Vac Phase voltage is 120Vac L1 N L2 N Parallel Operation in three phase The 31 setting item All connected...
Страница 33: ...pply is preferentially used to charge the battery Only when the Mains fails the PV charging can be activated 3 Hybrid charging PV and mains hybrid charging PV MPPT charging is a priority and when PV e...
Страница 34: ...and power supply Then the unit is equivalent to a backup UPS suitable for areas with unstable grid Switching does not affect PV charging Power supply priority Utility Solar Battery Battery priority mo...
Страница 35: ...d 4 operation buttons Operation buttons introduction Indicators introduction Function buttons Description SET Enter Exit Settings menu UP Previous choice DOWN Next choice ENT Confirm Enter Options und...
Страница 36: ...the machine has been connected to the battery indicates that the remaining battery is 0 24 indicates that the remaining battery is 25 49 indicates that the remaining battery is 50 74 indicates that t...
Страница 37: ...rter circuit This icon is not displayed Display battery voltage battery charge total current mains charge power AC input voltage AC input frequency PV input voltage internal heat sink temperature soft...
Страница 38: ...ge PV OUTPUT A PV output current 4 INPUT BATT A Input battery current OUTPUT BATT A Battery output current 5 INPUT BATT KW Battery input power OUTPUT BATT KW Battery output power 6 AC INPUT Hz AC inpu...
Страница 39: ...Parameter name Settings Description 00 Exit setting menu 00 ESC Exit the setup menu 01 Output source priority 01 SOL PV priority mode switching to the Mains when the PV fails or the battery is lower t...
Страница 40: ...en the mains charging fails the PV charging is started 06 SNU default PV and Mains hybrid charging PV charging is a priority and when the PV energy is insufficient the Mains charging supplements When...
Страница 41: ...ry 10 Battery boost charge time 10 120 default Boost charge maximum time setting which means the maximum charging time to reach the set voltage of parameter 09 during constant voltage charging The set...
Страница 42: ...isabled 16 ENA default Equalizing charge is enabled only valid for vented lead acid battery and sealed lead acid battery 17 Battery equalization voltage 17 58 4V default Equalizing charge voltage sett...
Страница 43: ...estart when over temperature is disabled If an over temperature shutdown occurs machine will not restart to turn the output on 24 ENA default Automatic restart when over temperature is enabled If an o...
Страница 44: ...ase Please refer to 2 4 Wiring Diagram When the parameter 38 setting item 120 for U series model All connected P1 phase inverters are set to 2P0 1 If all connected P2 phase inverters are set to 2P1 AC...
Страница 45: ...h BMS for the lithium battery protection PAC PACE RDA Ritar AOG ALLGRAND BATTERY OLT OLITER HWD SUNWODA DAQ DAKING WOW SRNE PYL PYLONTECH UOL WEILAN 35 Battery undervoltage recovery point 35 52V defau...
Страница 46: ...e voltage 55 2V 55 2V 55 2V 36 60V Adjustable Undervoltage alarm voltage 01 fault 44V 44V 44V 36 60V Adjustable Undervoltage alarm voltage recovery point 01 fault Undervoltage alarm voltage 0 8V Low v...
Страница 47: ...rge voltage 53 2V Adjustable 57 6V Adjustable 56 8V Adjustable 53 2V Adjustable 49 2 Adjustable Undervoltage alarm voltage 01 fault 43 6V Adjustable 46 8V Adjustable 49 6V Adjustable 46 4V Adjustable...
Страница 48: ...our company through this port and enables monitoring of the equipment running status and setting of some parameters on the computer RS485 1 RS485 2 also allows direct connection with the optional RS4...
Страница 49: ...nnect the female connector of the inverter to the male connector of the inverter to be paralleled d Do not connect the male connector of the inverter to its female connector Female connector Male conn...
Страница 50: ...V and the mains will be automatically stopped to charge the battery to prevent the battery from being overcharged and damaged 6 Battery low voltage protection When the battery voltage reaches the low...
Страница 51: ...ion loss protection In parallel operation an alarm will be given when CAN communication is lost 17 Parallel connection error protection In parallel operation the equipment will be protected when the p...
Страница 52: ...tware protection 03 BatOpen Yes Battery not connected alarm 04 BatLowEod Yes Battery undervoltage stop discharge alarm 05 BatOverCurrHw Yes Battery overcurrent hardware protection 06 BatOverVolt Yes C...
Страница 53: ...ad protection 15 AcOverCurrHw Yes Inverter overcurrent hardware protection 17 InvShort Yes Inverter short circuit protection 19 OverTemperMppt No Buck heat sink over temperature protection 20 OverTemp...
Страница 54: ...acityLowSto p Yes Inverter stops when battery capacity is low setting BMS to enable validity 34 CanCommFault Yes CAN communication fault in parallel operation 35 ParaAddrErr Yes Parallel ID setting er...
Страница 55: ...r 58 BMS communication error NO Check whether the communication line is connected correctly and whether 33 is set to the corresponding lithium battery communication protocol 59 BMS alarm NO Check the...
Страница 56: ...overload protection Reduce the use of power equipment Restart the unit to resume load output 17 Inverter short circuit protection Check the load connection carefully and clear the short circuit fault...
Страница 57: ...of high temperature or burning discoloration and tighten the screws 5 Check for dirt nesting insects and corrosion and clean up as required 6 If the arrester has failed replace in time to prevent lig...
Страница 58: ...ncy Range 47 0 3Hz 55 0 3Hz 50Hz 57 0 3Hz 65 0 3Hz 60Hz Overload short circuit protection Circuit breaker Efficiency 95 Conversion time bypass and inverter 10ms typical AC reverse protection Available...
Страница 59: ...Loaded motor capability 3HP 2HP Rated battery input voltage 48V Minimum starting voltage 44V Battery voltage range Undervoltage alarm shutdown voltage overvoltage alarm overvoltage recovery settable o...
Страница 60: ...ations AC charger PV charger Max charger current can be set 0 140A 0 120A Certified specifications Certification CE IEC 62109 1 CE IEC62109 1 CETL UL 1741 C22 2 NO 107 1 EMC certification level EN6100...