SPRSUN CGK/C H Series Скачать руководство пользователя страница 1

Heat Pump User Manual

Comprehensive version

Содержание CGK/C H Series

Страница 1: ...Heat Pump User Manual Comprehensive version...

Страница 2: ...r source heat pump heating cooling series CGK C XX HC CGK D XX HC 4 SP H Swimming pool heat pump heating series CGY C XX CGY D XX 5 SP HC Swimming pool heat pump heating and cooling series CGY C XX HC...

Страница 3: ...Pre start up 7 8 Part 2 Use 9 31 Operating panel display 9 12 Buttons function 13 14 Operating 14 15 Parameters query and setting 15 20 Error code 20 22 Working modes 25 26 Electrical component contro...

Страница 4: ...rations are done on the unit When the power cord gets looser or is damaged always get a qualified person to fix it Keep the unit away from the combustible or corrosive environment This appliance is no...

Страница 5: ...uct When running the unit never cover clothes plastic cloth or any other material that block ventilation on the product which will lead to low efficiency or even non operation of this unit When the po...

Страница 6: ...ir outlet to barrel distance should 2m air inlet distance to wall or barrel 0 5m bottom distance to ground 0 5m other side distance should be enough for installation or repairing Heat pump should be i...

Страница 7: ...5 2 Installation diagram and tips for reference only installation shall be based on actual project demand for hot water and floor heating...

Страница 8: ...ighest point of each water circulations for releasing air from water system A Y filter is very important in front of circulating water pump of heat pump If more heat pumps installed in one water pipe...

Страница 9: ...Check if the tank has been filled with water or enough water volume that can meet the demand of heat pump running Pre start up After check completely and confirm no problem for installation the unit...

Страница 10: ...8 Part 2 Use 1 Operating panel display HH series Single hot water mode Heating hot water mode...

Страница 11: ...9 SP H and SP HC series Heating mode...

Страница 12: ...10 Cooling mode HW series...

Страница 13: ...11 HT series 2 Buttons function Clock M power Power button 2 1 1 Under unlock state press this button for 1second can turn on and turn off heat pump...

Страница 14: ...ton can query and set parameter 2 2 3 Under power on state press and button can set current working mode water temperature except heating hot water mode Clock button 2 3 1 Press this button for 10seco...

Страница 15: ...heat pump Press power button if operating panel shows off state will turn on heat pump If operating panel shows on state will turn off heat pump Water tank temperature setting L3 or L4 Except HH seri...

Страница 16: ...oor heating water temperature only can be set by this way 4 Parameters query and setting operation Working status parameters and history error code query How to enter Under main interface press M butt...

Страница 17: ...er temperature Same meaning for all series A6 Return water temperature of water tank For HW and HT series Inlet water temp For HC and SP H and SP HC series Floor heating water temp For HH series displ...

Страница 18: ...eries E1 E6 History error code Same meaning for all series Note about water tank temp sensor installation position in each series is different A HW and HT series should be installed in hot water tank...

Страница 19: ...e B Under user parameter query interface press M button enter setting interface press and button to set the value of current parameter press M button again return query interface C Under user paramete...

Страница 20: ...ries 45 4 Other series 55 L4 Preset water tank temperature of cooling mode 8 32 12 Remarks for HC SP HC series L5 Ambient air temperature below which electric heater is allowed to start 25 25 5 L6 Ret...

Страница 21: ...g range upper limit F1 is different for different series 5 Error code Error code Meaning Er01 Wrong phase error Er02 Lack phase error Er03 Water flow switch error Er04 Anti freeze protection Er05 Outl...

Страница 22: ...ient air temp sensor error Er22 Return water temp sensor error from bathroom to water tank Remark For HW and HT series Inlet water temp sensor error Remark For HC SP H and SP HC series Floor heating w...

Страница 23: ...our press clock button then minute flash now press or button can set minute D After finish setting minute press clock button to confirm clock setting and back to main interface E At clock setting inte...

Страница 24: ...ting same way like ON timer setting E After finish setting group 1 ON OFF timer press clock button confirm group 1 setting and enter group 2 ON OFF timer setting same way like group 1 setting F At tim...

Страница 25: ...time reach preset quitting temperature can quit forced defrost way 2 forced quitting Press power button after power off 3minutes later will quit forced defrost completely Remove history error code At...

Страница 26: ...house have two working mode Hot water mode and hot water heating mode 2 1 Hot water mode controlling 2 1 1 When hot water tank temp L3 L2 hot water side starts 2 1 2 When hot water tank temp L3 hot wa...

Страница 27: ...p dropped L2 temp then heat pump stop and 3 way valve loss electricity then heat pump restart to heat hot water HC SP HC series The three series are all heating and cooling type User can change the wo...

Страница 28: ...should work at least 2min first then can stop Except turned off or there is error 1 4 There is not 3min protection for the first time starting Four way valve installed inside heat pump 2 1 At heating...

Страница 29: ...ally fan motor start in advance than compressor and stop at the same time as compressor 4 2 When defrosting fan motor doesn t work Auxiliary electrical heater 5 1 Starting conditions 5 1 1 At heating...

Страница 30: ...lectric heater will start Remarks HH series only hot water side has electric heater function heating side doesn t have Three way valve 6 1 Only HH heat pump have three way valve function Installer nee...

Страница 31: ...connects 8 1 2 Water tank temp L6 5 8 1 3 Return water temp L6 5 8 2 Condition of return water valve closes any below condition met 8 2 1 Low water level switch disconnects 8 2 2 Water tank temp L6 5...

Страница 32: ...olling as below 9 4 1 When low water level switch is disconnecting cool water compensating valve open 9 4 2 When low water level switch connects and high level switch disconnects according to below wo...

Страница 33: ...he signal 10 2 When operating panel is under on state if linkage signal is on heat pump keep on state If linkage signal is off heat pump will be turned off 10 3 When operating panel is under off state...

Страница 34: ...insulation damaged Check if the air around is clean and dry if ventilation is good Don t put debris around heat pump avoid blocking air inlet and outlet If need stop heat pump for long time should dra...

Страница 35: ...k should be done by qualified personal 2 If your units needs recharging then it has a leak only adding refrigerant will not solve the problem The leak must be located and repaired 3 Refrigerant should...

Страница 36: ...k if water tank temp probe is installed correctly 2 1 Release air from highest position of circulation 2 2 Open Y type filter to check if there is impurity on the net 3 Drain refrigerant and vacuum an...

Страница 37: ...water system 3 There is impurity in water filter 1 Change a bigger water pump 2 Release air from water system 3 Clean the filter Outlet water temp too high protection when heating hot water Er45 1 Cir...

Страница 38: ...er is dirty 4 Water heat exchanger scaled 1 Check leakage and repair and refill gas 2 Improve the insulation 3 Clean air heat exchanger 4 Clean water heat exchanger 3 Compressor doesn t run 1 Power su...

Страница 39: ...blade fixing screw is loose 2 Fan motor damaged 3 Fan motor capacitance damaged 1 Tight the screw 2 Change fan motor 3 Change the capacitance 6 Compressor run but not heat 1 There is not refrigerant a...