1.1.4 Overload trip
The 200XLV has an overload-inverse time-trip device (Figures 4 and 5).
200
400
600
Approximate trip time (s)
100%
Maximum current limit
800
110%
130%
150%
120%
140%
20
25
30
Ambient temperature
25%
Maximum continuous
current (approx.)
1000 s
35
40°C
50%
75%
100%
Figure 4 Maximum
continuous current vs
ambient temperature
Figure 5 Trip
time vs maximum
current limit
Excessive overload will trigger the device, causing the READY lamp to switch off. To reset the
trip, remove the power from the unit for a few seconds.
NOTE: Fit a multi-fuse to provide a lower threshold if small motors are used (refer to "8.3