Accessories
D.1.4
Range
Table 25: Sensitivity Ranges
Sensitivity
Detection Sensitivity
Setting (ft/m)
Maximum Testing Distance
(ft/m)
40/40R
50/15
4/1.2
Notes:
•
The minimum distance from the detector is 20
”/
50cm.
•
At extreme temperatures, there is a 15% maximum reduction in
the range.
Warning:
Keep the flame simulator in a safe place when not in use.
D.1.5
Charging the Battery
The flame simulator uses lithium-ion batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates at least 1,000 times
without having to be recharged. The simulator will not operate when the voltage
from the batteries is lower than the required operational level.
1
Simulator
3
Locking Disc
2
Battery Pack
4
Back Cover
Figure 15: Flame Simulator Battery Replacement