Specifications
A.6.5
Dust
•
Designed to meet MIL-STD-810C, Method 510.1, Procedure I
•
Exposure to a dust concentration of 0.3g/ft
2
at a velocity of 1750fpm, for 12
hours
A.6.6
Vibration
•
Designed to meet MIL-STD-810C, Method 514.2, Procedure VIII
•
Vibration at an acceleration of 1.1g within the frequency range of 5
–
30Hz,
and an acceleration of 3g within the frequency range of 30
–
500Hz
A.6.7
Mechanical Shock
•
Designed to meet MIL-STD-810C, Method 516.2, Procedure I
•
Mechanical Shock of 30g half-sine wave, for 11 msec
A.6.8
Electromagnetic Compatibility (EMC)
Table 21: Electromagnetic Compatibility (EMC)
Test Standard
Level Per
Electrostatic Discharge ESD
IEC 61000-4-2
EN 50130-4
Radiated EM Field
IEC 61000-4-3
EN 50130-4
Electrical Fast Transients
IEC 61000-4-4
EN 50130-4
Surge
IEC 61000-4-5
EN 50130-4
Conducted Disturbances
IEC 61000-4-6
EN 50130-4
Power Frequency Magnetic Field
IEC 61000-4-8
EN 50130-4
Radiated Emission
IEC 61000-6-3
EN 55022
Conducted Emission
IEC 61000-6-3
EN 55022
Immunity to Main Supply
Voltage Variations
IEC 61000-4-29
EN 50130-4
Caution:
To fully comply with EMC directive 2014/30/EU and protect against
interference caused by RFI and EMI, the cable to the detector must be
shielded and the detector must be grounded. The shield should be
grounded at the detector end.