Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
76
Flame Simulator FS-1400
D.1.1 Ordering Information
The P/N of the Flame Simulator Kit is 380114-4.
The kit is supplied in a carry case that includes:
Flame Simulator FS-1400
Charger
Tool Kit
Technical Manual TM380302
D.1.2 Unpacking
Verify that you have received the following contents:
Delivery form
Flame simulator with integral battery
Battery charger
Tool keys
User manual
FAT forms
EU declaration
Storage case
D.1.3 Operating Instructions
Warning
: Do not open the flame simulator to charge the batteries or for
any other reason in a hazardous area.
Caution
: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If activation is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
➣
To simulate a fire:
1
Verify you are at the correct distance from the detector according to the
type of detector and the detector sensitivity.
2
Using the mechanical sight, aim the flame simulator toward the center of
the detector.
3
Push the activate button, and then use the laser spot for fine adjustment
toward the center of the detector.
4
Keep the simulator aimed at the detector for up to 50 seconds, until you
trigger an alarm.
5
Wait 20 seconds before repeating the test.
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......