Product Overview
TM40/40L Rev. (Ag), February 2019
23
•
Inmetro (UL), page 24
•
TR CU/EAC, page 24
2.4.5.2
ATEX, IECEx
The 40/40L, LB, L4, L4B Flame Detector is certified to:
ATEX per SIRA 07ATEX1250X and IECEx per IECEx SIR 07.0085X
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96°C Db
(
–55°C ≤ Ta ≤ +75°C)
Or
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db
(
–55°C ≤ Ta ≤ +
85°C)
The accessories, Tilt Mount P/N 40/40-001, Weather Cover P/N 777163 and P/N
777268, Duct Mount P/N 777670, and Air Shield P/N 777650 are included in the
approval.
This product is suitable for use in hazardous Zones 1 and 2 with IIC gas group
vapors present, and Zones 21 and 22 with IIIC dust type present.
2.4.5.3
FM, CSA
The 40/40L, LB, L4, L4B Flame Detectors are approved per FM and CSA Explosion
Proof and Functionality per FM3260:
•
Class I, Division 1, Groups B, C and D.
•
Dust Ignition Proof
–
Class II/III Division 1, Groups E, F and G.
•
Ingress Protection
–
IP67, IP66, NEMA 250 Type 6P.
•
For more details see
FM Report Project ID3029553
, and
CSA Report No.
2451134
.