![Spectrex SHARPEYE 20 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/spectrex/sharpeye-20/sharpeye-20_user-manual_1344014058.webp)
Operation
58
SharpEye
TM
IR3 Flame Detector User Guide
B.2
Operation
Figure 17: Mini IR3 Detector Target Point
Warning
: Do not open the flame simulator to charge the batteries or for any
other reason in a hazardous area.
Caution:
The following test will simulate a real fire
condition and may activate the extinguishing
system or other alarms. If this is not desired,
disconnect/inhibit them before the test and
reconnect
after the simulation.
To simulate a fire:
1
Stay at a distance of at least 50cm/20
”
from the detector.
2
Using the mechanical sight, aim the flame simulator toward the target
point of the detector.
3
Press the operation button once. The flame simulation will last for 20
seconds. The detector will send an alarm signal (solid red LED).
4
Wait 20 seconds before repeating the test.
5
Make sure the optical window is clean and keep the Flame Simulator in
a safe place when not in use.