Wiring Option Configurations
70
SafEye
TM
Xenon 700S Gas Detector User Guide
Figure 13: 0–20mA Wiring (Source) For Wiring Options 1 and 3
Notes:
The detectors are factory set to isolated 0–20mA-sink version.
For non-isolated 0–20mA version (source), connect Terminal 8 to
Terminal 1. The 0–20mA meter is connected between Terminal 7 and
Terminal 2.
Figure 14: 0–20mA 3 Wire Connection for Options 1 and 3
Содержание SafEye Xenon 700S
Страница 2: ...This page intentionally left blank ...
Страница 12: ......
Страница 16: ......
Страница 24: ...Models and Types 24 SafEyeTM Xenon 700S Gas Detector User Guide Figure 1 Wiring Options ...
Страница 64: ......
Страница 72: ......
Страница 76: ......
Страница 79: ...This page intentionally left blank ...