Maintaining Your Detector
TM888050 Rev. (Da), October 2017
31
6
Maintaining Your Detector
The SafEye Quasar™ system requires only simple periodic maintenance to
provide satisfactory service and achieve maximum performance.
The detector and source units can be maintained with the use of standard tools
and equipment. It is recommended that you record the periodic test results in a
maintenance logbook.
To maintain your detector:
Clean the optical surfaces of the detector and source once a month.
Perform alignment and calibration once every six months, or after each time
the units are moved or opened.
To clean the optical surfaces:
Turn off the detector.
In places where dust or dirt have accumulated on the optical surface, clean
the surface with a small soft bristle brush.
Wash the surfaces thoroughly with water and a mild non-abrasive detergent.
Thoroughly rinse the glass surface with clean water, ensuring no residue is
left behind.
Dry the glass with a clean dry soft cloth.
Enter the following information into the maintenance log: date and name of
person and company who performed the maintenance service.
Turn on the detector.
Perform zero calibration.