Periodic Maintenance
TM794200
Rev Ad, March 2019
61
➢
To check signal intensity:
1
Enter alignment mode by placing the mode selector on the side of the
detector for 2 seconds.
2
Within the first 20 seconds the detector indicates 3 different indication
levels (see Table 2).
3
Wait 20 seconds, count the number of LED flashes, and note the
colors. Then adjust the value (see Table 13).
4
Record the new results in the maintenance logbook.
5
Wait 20 seconds, count the number of LED flashes, and note the
colors. Then adjust the value (see Table 13).
6
Record the new results in the maintenance logbook.
7
Determine the absolute variance compared with the previous
alignment reading in the maintenance logbook.
8
If the variance is more than 30%, perform alignment (see
on page 55) and zero calibration (see
page 56). Call a technician for service if the SIC is less than 66 and
both LEDs flash red.
Table 13: LED Signal Adjustment
Color (left-right)
Number to be added
Red-Red
0
Orange-Orange
62
Green-Orange
124
Green-Green
186
Example:
At a hypothetical installation, the LEDs are green-orange with 3 green
flashes (left LED) and 6 orange flashes (right LED).
The number is 36 + 124 = 160
The next periodic maintenance reading has orange-orange LEDs with 8
orange blinks (left LED) and 8 orange flashes (right LED).
The number is 88 + 62 = 150
The variance is 160 - 150 = 10 Units
The percentage of variance will be (10/160) x 100 = 6.25% less than the
previous alignment.
Содержание SafEye 300 Series
Страница 2: ......
Страница 10: ......
Страница 32: ......
Страница 58: ......
Страница 64: ......
Страница 67: ...TM794200 Rev Ad March 2019 67 Appendix B Wiring Option Configurations Figure 13 Detector Wiring Diagram ...
Страница 70: ......
Страница 71: ...TM794200 Rev Ad March 2019 71 Appendix C Outline Drawings ...
Страница 72: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......