Spectra 1759ex Скачать руководство пользователя страница 7

S

PECTRA

 1759EX 

  5

2.5

AUXILIARY POWER TERMINALS*

The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the 
security system. A fuseless circuit protects the power supply against current overload and automatically shuts down if the current 
exceeds 1.1A. If this occurs, the Maximum Auxiliary Current failure will appear in the keypads’ Trouble Display (see page 42). 
Therefore, the combined current consumption of devices connected to the auxiliary power supply should not exceed 700mA. If 
the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before 
reconnecting any load back to the auxiliary output.

Modules with the APR- prefix are compatible with the Spectra 1759EX and Digiplex. Modules with the APR3- prefix are 
compatible with the Spectra 1759EX, Digiplex and DigiplexNE.

2.6

TELEPHONE LINE CONNECTION

In order to report system events to the central station, you must connect the incoming telephone company wires into the TIP and 
RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as shown in 
Figure 2.2 on page 4.

2.7

BELL OUTPUT CONNECTION

The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm. 
The bell output supplies 12VDC upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless 
circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will only 
appear in the keypads’ Trouble Display (see page 42) during an alarm. If the load on the BELL terminals returns to normal, the 
control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens, please verify correct 
polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the control panel as 
shown in Figure 2.2 on page 4.   

If the BELL output is not being used, the Bell Disconnected failure will remain in the keypads’ Trouble Display 
(see page 42
). To avoid this connect a 1K

 resistor across the BELL terminals. 

2.8

PROGRAMMABLE OUTPUT CONNECTIONS*

When a specific event occurs in the system, a PGM can reset smoke detectors, activate strobe lights, open/close garage doors 
and much more.

2.8.1

A

LARM

 R

ELAY

 

AND

 PGM

S

 

The Spectra 1759EX control panel includes two on-board programmable outputs (PGMs). For details on how to 
program the PGM, refer to 

PGM Programming

 on page 35. PGM1 can support up to 150mA while PGM2 supports up 

to 1A (see Figure 2.3 on page 6) and can be used as a strobe output (see page 36). The PGMs are limited by the 
power source being used. If powered by:

The 

AUX

 terminals.

 The current consumption of the 

AUX

 terminals cannot exceed 700mA. Therefore, whatever 

devices are connected to the 

AUX

 terminals (i.e. modules and PGMs) cannot exceed 700mA combined. For 

example, if there are six modules connected to the 

AUX

 terminals that are using 600mA and you wish to power the 

PGM using the 

AUX

 terminals, the PGM’s current consumption will not 100mA.

An external power supply.

 If using an external power supply, the current consumption cannot exceed 150mA for 

PGM1 and 1A for PGM2. If the external power supply’s current consumption limit is less than that of the PGM it is 
connected to, than the current consumption will not exceed the power supply’s current limit.  

The Spectra 1759EX control panel also has a 5A relay. This relay can be connected as shown in Figure 2.3 on page 6. 
The Alarm Relay can be programmed to follow the bell output or the activation and deactivation of the Global PGM 
(see 

Alarm Relay Options

 on page 36).

* UL Note: The AUX and PGM terminals cannot exceed 200mA for UL installations.

Table 2: 

Current Consumption Table

Modules

Current Consumption

Typical

Maximum

Spectra 1686H and 1686V 10-Zone LED Keypad

62mA

 116mA

Spectra 1689 16-Zone LED Keypad

50mA

 117mA

Spectra 1641 LCD Keypad

60mA

 80mA

4-Zone Hardwire Modules (APR3-ZX4/SPC-ZX4)

12mA

 12mA

8-Zone Hardwire Modules (APR3-ZX8/SPC-ZX8)

30mA

 30mA

4-PGM Output Module (APR3-PGM4)

13mA

 150mA

Printer Module (APR3-PRT1)

22mA

 40mA

InTouch Voice-Assisted Arm/Disarm Module (APR3-ADM2)

70mA

105mA

Motion Detectors (see detector instructions for details)

10 to 50mA

Содержание 1759ex

Страница 1: ...1759EX V1 0 REFERENCE INSTALLATION MANUAL 433MHZ 868MHZ 1759EX...

Страница 2: ......

Страница 3: ...e Alarm 26 Tamper Recognition 26 Keypad Panic Options 27 Panic Lockout Timer 27 Reporting and Dialer settings 28 Reporting Dialer Enable Disable 29 Report Codes 29 Central Station Telephone Numbers 31...

Страница 4: ...nsmission and Recent Closing Report Regular Arming Stay Arming Instant Arming Force Arming One Touch Arming Auto Arming or Keyswitch Arming 256 Event Buffer with time stamp Telephone Line Supervision...

Страница 5: ...2 2 on page 4 For UL installations the metallic enclosure must be grounded to the cold water pipe 2 3 AC POWER Do not use any switch controlled outlets to power the transformer Connect the transformer...

Страница 6: ...AC Power and Backup Battery Connections on page 3 To connect the 5A Alarm Relay and the PGMs refer to Relay and PGM Connections on page 6 To connect AC power refer to AC Power and Backup Battery Conne...

Страница 7: ...Bell Disconnected failure will remain in the keypads Trouble Display see page 42 To avoid this connect a 1K resistor across the BELL terminals 2 8 PROGRAMMABLE OUTPUT CONNECTIONS When a specific event...

Страница 8: ...trol panel remove the back cover and wire the GRN YEL RED and BLK terminals of each keypad to the corresponding terminals on the control panel as shown in Figure 2 2 on page 4 There is no limit to the...

Страница 9: ...or by activating a switch with a key Connect the keyswitch as shown in Figure 2 6 directly to the control panel terminals Once a keyswitch is connected it must be assigned to a zone and its parameters...

Страница 10: ...sections 001 to 016 126 to 138 and 302 to 348 each option from 1 to 8 represents a specific feature or option Press the key corresponding to the desired option and the corresponding light will illumin...

Страница 11: ...hen key 2 is OFF not illuminated EOL is disabled and the keypad zone will use the on board EOL resistor When key 2 is ON illuminated EOL is enabled and the keypad zone requires that an external EOL re...

Страница 12: ...ory Key PMC 3 Then copy the contents of the Memory Key into as many Spectra control panels as needed Each panel is programmed in less than 3 seconds Download to DESTINATION Control Panel 1 Remove AC a...

Страница 13: ...s The System Master Code can be 4 or 6 digits in length Access Code Length on page 11 where each digit can be any digit from 0 to 9 To change the System Master Code press ENTER INSTALLER CODE 301 new...

Страница 14: ...is dependent on the other User Code Options selected Please note that with the Arm Only option the user can cancel a recently armed system by re entering the access code before the end of the Exit Del...

Страница 15: ...to the same expansion input 5 2 REASSIGN KEYPAD ZONE 2 Section 126 General Options Option 7 OFF Reassign Keypad Zone 2 Disabled default Option 7 ON Reassign Keypad Zone 2 Enabled Reassign Keypad Zone...

Страница 16: ...s partition assignment and how the control panel will react when an alarm condition occurs on that zone These Zone Parameters are programmed into one section as detailed in Figure 5 1 on page 15 Only...

Страница 17: ...e a different Entry Delay 5 5 2 ENTRY DELAY 2 Sections 001 to 015 Zones 1 to 15 First Digit 2 Entry Delay 2 zones are identical to the Entry Delay 1 zones see section 5 5 1 except it uses a separate E...

Страница 18: ...5 6 EXCLUSIVE ZONE DEFINITIONS The following three zone definitions can only be used for devices connected directly to the control panel s on board input terminals When a zone is programmed as a Keys...

Страница 19: ...S ZONES Sections 001 to 015 Zones 1 to 15 Option 2 OFF Bypass Zone Disabled Option 2 ON Selected Zone is Bypass Enabled default When a user utilizes the Bypass Programming feature see page 45 only zon...

Страница 20: ...5 Option 8 OFF Force Zone Disabled default Option 8 ON Selected Zone is Force Enabled Any open Force Zones at the time of arming will be considered deactivated by the control panel see page 45 If duri...

Страница 21: ...re proper synchronization between the control panel and the transmitter open and close the zone corresponding to the transmitter 6 1 2 DELETING ASSIGNED WIRELESS TRANSMITTERS Sections 601 to 608 6 1 3...

Страница 22: ...ignal within a specified time period as programmed in Check in Supervision Timer Settings on page 21 to confirm their presence and functionality If a device has not sent a signal within that time peri...

Страница 23: ...ore information refer to Wireless Transmitter Low Battery Supervision on page 40 6 5 REMOTE CONTROL PROGRAMMING The Spectra 1759EX accepts up to eight fully programmable remote controls Programming th...

Страница 24: ...ned to sections 731 to 738 refer to Assigning a Remote Control to the Spectra 1759EX on page 21 For example the buttons for the remote control assigned in section 731 will be programmed in section 711...

Страница 25: ..._ ____ ____ A B C D A B C D A C B D Remote Control 4 715 ____ ____ ____ ____ ____ ____ ____ ____ A B C D A B C D A C B D Remote Control 5 716 ____ ____ ____ ____ ____ ____ ____ ____ A B C D A B C D A...

Страница 26: ...feature allows users to Force arm without pressing the FORCE key before entering their User Access Code Force arming cannot be done using a keyswitch Force arming is not supported by keyswitches 7 4 R...

Страница 27: ...terval of time without movement you wish the control panel to wait before arming and or sending the No Movement report code If No Movement Auto Arming is disabled the control panel can still send the...

Страница 28: ...Option 5 ON No Exit Delay Beeps and No Bell Squawk When Stay Arming Enabled With this feature enabled the control panel will prevent the bell or siren from squawking and the keypads from beeping duri...

Страница 29: ...F Emergency Panic Disabled default Option 1 ON Emergency Panic Enabled Press the 1 and 3 keys simultaneously on the keypad for 2 seconds to generate a silent or audible alarm as defined by option 4 Op...

Страница 30: ...Codes Option 6 ON Call Telephone 2 for Tamper Restore Report Codes Section 138 Option 1 ON Call Telephone 1 for Trouble Restore Report Codes Option 2 ON Call Telephone 2 for Trouble Restore Report Cod...

Страница 31: ...ARMING A partition has armed itself at the programmed time see page 24 LATE TO CLOSE Reports every day at the time specified by the Auto Arm Timer see page 25 NO MOVEMENT A partition has armed itself...

Страница 32: ...T CODES Sections 201 to 204 A report code can be programmed for each of the 15 available zones Whenever a tampered zone is restored the control panel can send the appropriate report code to the centra...

Страница 33: ...these telephone numbers are used please refer to Event Call Direction on page 33 and Reporting Formats on page 31 After the Maximum Dialing Attempts see page 34 to one central station telephone numbe...

Страница 34: ...trol panel will automatically generate Contact ID Report Codes for every event in sections 160 to 213 Refer to the All Codes Ademco Contact ID Report Code List in the Spectra System Programming Guide...

Страница 35: ...ption 3 is off and option 4 is on in section 137 the control panel will attempt to communicate with Central Station Telephone Number 2 in order to transmit the Zone 1 Alarm Report Code programmed in s...

Страница 36: ...generated within the period defined by the Recent Close Delay the control panel will attempt to transmit the Recent Close report code programmed in section 195 9 16 AUTO TEST REPORT Sections 087 000 D...

Страница 37: ...e for the duration of this period the control panel will generate the condition s defined by the TLM options see above PART 10 PROGRAMMABLE OUTPUTS A PGM is a programmable output that toggles to its o...

Страница 38: ...t has occurred in the system You can program each PGM output to be normally open N O or normally closed N C by enabling or disabling options 4 5 and 6 in section 126 Option 4 OFF PGM1 Normally Closed...

Страница 39: ...Charge Current 350mA default Option 5 ON Battery Charge Current 700mA 40VA transformer required 11 5 PARTITIONING Section 127 General Options Option 1 OFF Partitioning Disabled default Option 1 ON Pa...

Страница 40: ...el will send the Zone Tamper report code as originating from partition 1 A Tamper Zone Wiring Failure will also appear in the keypads Trouble Display see page 42 When Reassign Keypad Zone 2 is enabled...

Страница 41: ...ith the APR prefix are compatible with Spectra versions 2 0 and higher and Digiplex Modules with the APR3 prefix are compatible with Spectra versions 2 0 and higher Digiplex and DigiplexNE 11 13 PRINT...

Страница 42: ...panel will follow the zone s Alarm Types setting see page 17 7 ON 8 ON Audible Alarm When a tamper occurs on an Omnia wireless transmitter zone in a disarmed system it functions the same as the Troubl...

Страница 43: ...rings This value represents the number of rings the control panel will wait before picking up the line If the line is not answered after the number of programmed rings the control panel will answer t...

Страница 44: ...lls back Please note that the PC Telephone Number must be programmed in section 150 in order to use the Call Back feature PART 13 USER OPERATION 13 1 TROUBLE DISPLAY The Spectra system continuously mo...

Страница 45: ...communicate with the central monitoring station 8 Timer Loss The control panel s internal clock must be re programmed To re program the timer press the 8 key followed by the current time using the 24...

Страница 46: ...MASTER CODE or MASTER CODE 3 Key in 3 digit SECTION see Table below 4 Key in new 4 or 6 digit ACCESS CODE ENTER flashes Return to step 3 How Do I Delete Access Codes 1 Repeat steps 1 to 3 see above 2...

Страница 47: ...ust have the Force Arming Option enabled 13 8 MANUAL BYPASS PROGRAMMING Manual Bypass Programming allows users to program the alarm system to ignore deactivate specified zones the next time the system...

Страница 48: ...Press and hold keys 1 and 3 for a panic alarm Press and hold keys 4 and 6 for a panic or medical alarm Press and hold keys 7 and 9 for a panic or fire alarm 13 12 AUTO ARMING NOT TO BE USED WITH UL IN...

Страница 49: ...ation Beep All other beep functions are disabled 13 16 KEYPAD BACKLIGHT 1686H and 1686V Only The illumination level behind the keys can be modified to suit the user s needs There are four backlight le...

Страница 50: ...munications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to equipment intermittently the user is encour...

Страница 51: ...circuit boucl peut tre constitu e de n importe quelle combinaison de dispositifs pourvu que la somme des indices de charge de l ensemble des dispositifs ne d passe pas 100 La certification d Industri...

Страница 52: ...tion 5 Bell Squawk On Arm Disarm With Keypad 26 Bell Squawk On Arm disarm with Remote Control 26 Burglary Zones 24 Hr 16 Buzzer Zone 16 Bypass Options Supervision 40 Bypass Programming 45 Bypass Recal...

Страница 53: ...rming On Battery Fail 24 No Arming on Supervision Loss 40 No Arming On Tamper Trouble 24 No Audible Feedback Upon Stay Arming 26 No Exit Delay When Arming with Remote Control 26 No Movement Auto Armin...

Страница 54: ...ne Line Connection 5 Telephone Line Monitoring TLM 35 Telephone Number PC 41 Telephone Numbers 31 Test Report Automatic 34 Test Report Manual 39 Timed Auto Arming 24 Transformer Requirements 3 Transmi...

Страница 55: ......

Страница 56: ...to Friday 8 a m to 8 p m EST Technical support can also be reached by fax at 450 491 2313 or via e mail at support paradox ca 780 Industriel Blvd Saint Eustache Quebec J7R 5V3 CANADA Tel 450 491 7444...

Отзывы: