INSTRUCTION MANUAL

XP2 Series, Conduit Style

Active Speed Sensors

85047X

Engineering Approval:

Date:  03-18-2019

Revision:  1

PROPRIETARY, COPYRIGHTED INFORMATION DO NOT DUPLICATE OR DISTRIBUTE TO THIRD PARITES UNLESS AUTHORIZED BY SPECTEC

Approval agency controlled document. Do not alter without authorization.

Page 1 of 3

Introduction

SPECTEC's Explosion Proof / Flame Proof sensors are designed for
installation in hazardous locations. They are offered in a wide
variety of configurations. See the XP2 Bulletin for specifications

and configuration options.

Marking

Unit Type No.:

XP2-xxxxxx

Date Code:

WW/YY (Week/Year)

Conduit Size:

1/2- NPT or M20x1.5

Electrical Rating: xx to xx V DC @ 

xx mA (marked according to

sensor type, see XP2 Bulletin)

Codes:

CL I DIV 1 GP ABCD T6...T3
CL I ZN 1 AEx/Ex db IIC T6...T3 Gb

T3@ Ta = -50°C...+140°C (marked)
T4@ Ta = -50°C...+112°C
T5@ Ta = -50°C...+77°C
T6@ Ta = -50°C...+62°C

     II 2 G Ex db IIC T6...T3 Gb
T3@ Ta = -55°C...+140°C (marked)
T4@ Ta = -55°C...+112°C
T5@ Ta = -55°C...+77°C
T6@ Ta = -55°C...+62°C

Certificate No.:

FM16US0288X & FM16CA0147X
FM16ATEX0086X & IECEx FMG 16.0035X

CE Marking:

        2809

Warnings:

SEAL ALL CONDUITS WITHIN 18 INCHES

DISCONNECT POWER BEFORE OPENING
FERMER TOUS LES CONDUITS SOUS 18 POUCES

(.45m) MAXIMUM

DÉBRANCHER L’ALIMENTATION ELECTRIQUE

AVANT L'OUVERTURE

Specific Conditions of Use

1. Refer to these instructions for complete temperature ratings

and suitability.

2. No external grounding is provided. The sensor must be

mounted as part of a bonded structure.

3. The wiring shall be mechanically protected as required by the

applicable area electrical code and shall be terminated in a
suitable terminal or junction facility.

Warnings

1. A poured conduit seal must be applied within 18 inches

(0.45m) of the sensor.

2. Disconnect power before opening or removing the sensor.

Compatibility

Refer to the listed certification and temperature ratings for

suitability. The intended environmental and operating conditions
should be verified to be in compliance with these ratings.

Housing:  303 or 304 series Stainless Steel

Cable:

PTFE insulated (Polytetrafluoroethylene)

or FEP insulated (Fluorinated ethylene propylene)

NOTE:

 For Canadian installations, only female NPT or metric entries

are permissible per CSA C22.2 No. 0.5 & 30.

Type Approval Standards

The XP2 product series have certificates issued by FM Approvals

and have been approved to the following standards:

United States of America (USA) Standards:

FM Class 3600:2011

General Requirements

FM Class 3615:2006

Explosionproof General Requirements

FM Class 3810:2005

General Requirements

ANSI/ISA61010-1:2012

Safety General Requirements

ANSI/ISA60079-0:2013

General Requirements

ANIS/UL60079-1:2015

Flameproof Enclosures 'd'

Canadian Standards:

CSA C22.2 No. 0.4-04: R2013

Bonding of Electrical Equipment

CSA C22.2 No. 0.5:2016

Threaded Conduit Entries

CSA C22.2 No. 61010-1:2012

Safety General Requirements

CSA C22.2 No. 30-M1986:R2012

Explosion-proof Encl.

CSA C22.2 No. 60079-0:2012

General Requirements

CSA C22.2 No. 60079-1:2016

Flameproof Enclosures 'd'

ATEX Standards:

EN60079-0:2012 + A11:2013

General Requirements

EN60079-1:2014

Flameproof Enclosures 'd'

IECEX Standards:

IEC60079-0:2011

General Requirements

IEC60079-1:2014

Flameproof Enclosures 'd'

Installation Requirements

The installation shall be carried out by suitably trained personnel.
The sensor must be installed in accordance with the latest issue of
the following standards:

US installations:

follow the National Electrical Code ANSI/NFPA 70,

Canadian installations:

follow the Canadian Electrical Code CSA C22.1,

ATEX installations: follow EN 60079-14,

IECEx installations: follow IEC 60079-14.

The installation must also be in accordance with any local codes

and national regulations that apply.