NST13165-2_A 2019-02-12
Page 3
MOD-QC TEST INPUTS - ALL DOORS SHOULD BE CLOSED
Any time the Antenna/Reader is powered-up, the Mod-QC Test is executed and takes about
30-seconds. The red and green status LEDs emit a series of flashes which indicate the status of the
inputs to the Antenna/Reader. The Mod-QC Test interrogates the Antenna/Reader location inputs, the
data bus input and the inputs to the unlock switch and the RFID circuit. The Curbside door is the
Master Node which controls ALL of the data traffic.
DOOR LOCATION - First QC Test (5-10 Seconds)
Note: the red LED will flash the location sequence twice
Curbside Door 1-flash or single flash
Bulkhead Door 3-flashes or triple flash
Rear Door 4-flashes or quad flash
DATA BUS - Second QC Test (10 Seconds)
If the data bus on the Bulkhead and Rear door Antenna/Readers is communicating with the Curbside
door (the master node), the red LED will flicker-flash for 10-seconds. If you are testing the Curbside
door, the red LED will flicker-flash for about 3-seconds then be off for about 7-seconds.
INPUTS - Third QC Test (15 Seconds)
In this test, each of the inputs is tested: the RFID circuit and the unlock switch input.
RFID
Present any RFID key (Keychain Tag) to the Antenna/Reader. It does not need to be enrolled.
When any Tag is detected, both LEDs will turn off and back on when the Tag is removed.
UNLOCK SWITCH
Press the unlock switch. If the unlock switch input is detected, the green LED will turn off and
back on when the switch is released.
KEYLESS ENTRY