Servicing Fan Modules
The four fan modules in the server are located at the front of the chassis. See
. You can access the fan modules without removing the server cover.
You might need to extend the server from the rack to access the fans. Each fan module contains
two fans mounted in an integrated, hot-serviceable component.
These topics describe how to service faulty fan modules.
■
■
“Determine Which Fan Module Is Faulty” on page 79
■
“Remove a Fan Module” on page 79
■
“Install a Fan Module” on page 82
■
“Verify a Fan Module” on page 85
Related Information
■
“Preparing for Service” on page 45
Servicing Fan Modules