7.5.2

Disconnect both the black H.T. lead and the grey flame sensor lead from the electrode assembly.

 
7.5.3

Unscrew the four M4 screws securing the injector holder to the venturi inlet and remove the complete control
assembly.   Take care to retain the orifice plate, (if fitted) located between the injector holder and the venturi.

 
7.5.4

Disconnect the appliance from its suspension means, lower to ground level and place on a workbench with the
emitter uppermost.

7.5.5

Unscrew the two M5 nuts securing the electrode mounting plate to the appliance side panel and withdraw the
electrode assembly.

7.5.6

Support the plenum box assembly and remove the two M5 setscrews securing it (and the electrode assembly) to the
appliance side panel.  Lower the plenum box assembly to rest on the reflector cowling.

7.5.7

Unscrew the M5 nut securing the plenum box support bracket to the opposite side panel of the appliance and, lifting
this end of the plenum box assembly clear of the appliance side panel, withdraw the plenum box assembly, taking
care when passing the venturi through the adjacent side panel.

 
7.5.8

Place the plenum box assembly on the bench with the reverberatory screen uppermost and remove the screen
panels, as necessary by twisting the securing tabs (at underside of plenum box flange) in line with the slots in the
flange, through which they pass, and lift off.

7.6

Emitter Assembly (ceramic tiles)

7.6.1

In the unlikely event that a ceramic tile is damaged and requires replacement, contact Space-Ray at the address
shown on the front cover of this manual.

7.7

Replacement Parts List

The following is a list of replacement parts which may be required during the life of the appliance.

Description

Part Number

Description

Part Number

H.T. Lead Assembly

4250584A

Solenoid Actuator - HI/LO

4262706

Flame Sensor Lead

4250584J

Reverb. Screen Panel

4262731

Ignition Control

4262534

Electrode Assembly

4262732

Control Valve

4262586

8.

OPERATING INSTRUCTIONS

8.1

Turn on the gas supply to the appliance.

8.2

Set any time switch or thermostats to demand heat.

8.3

Switch on the electrical supply to the appliance.

8.4

The burner should ignite within 25 seconds.

8.5

Failure to ignite will result in the ignition controller going to "Lockout" condition.

8.6

If 'Lockout' occurs, switch off the electrical supply to the appliance, wait for 10 seconds before switching on the
electrical supply to the appliance to repeat the ignition sequence.

8.7

If the appliance fails to ignite after a second sequence, switch off the electricity supply to the appliance and call the
service engineer.

8.8

If gas failure occurs after successful ignition, the appliance will attempt one re-ignition before going to "Lockout"
conditions.

8.9

To shut down the appliance for short periods of time, switch off the electricity supply to the appliance.

8.10

To shut down the appliance for longer periods of time switch off the electricity supply to the appliance and turn off
the gas supply at the gas isolation valve.

Содержание Ultra 14

Страница 1: ...S Ultra 7 Ultra 7 3 5 HI LO Ultra 14 Ultra 14 7 HI LO Ultra 21 Ultra 21 10 5 HI LO Ultra 28 Ultra 28 14 HI LO Ultra 42 Ultra 42 21 HI LO Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk I...

Страница 2: ......

Страница 3: ...2 Ultra 7 14 21 28 42 12 4 3 Ultra 7 3 5 14 7 21 10 5 28 14 42 21 12 5 Commissioning 13 14 5 1 Ignition 13 5 2 Shut Down 13 5 3 Checking Gas Pressure 13 14 5 4 Flame Supervision 14 6 Servicing 15 16...

Страница 4: ...Qn 13 33 kW Hs 12 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40m...

Страница 5: ...50Hz 25W Fuse Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 5 MODEL Ultra 42 N Ultra 42 L Heat Input Qn 39 96 kW Hs 36 0 kW Hi 37 74 0 kW Hs 34 0kW Hi Appliance...

Страница 6: ...6 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40mm Electrical Sup...

Страница 7: ...use Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 10 MODEL Ultra 42 21 HI LO N Ultra 42 21 HI LO L Heat Input Qn 39 96 kW 19 98 kW Hs 37 74 kW 18 87kW Hs 36 00...

Страница 8: ...it is recommended that suitable protected welded chain 3mm x 65 links m or 6mm minimum mild steel drop rods and suitable brackets are used Attach the chains or drop rods to the 4 suspension screws of...

Страница 9: ...itted in accordance with National and Local Regulations Pipes of a smaller size than the appliance connection Rc should not be used and the pipework must be designed to achieve the nominal gas supply...

Страница 10: ...pliance must be installed in accordance with the latest or current National Regulations and any Local Regulations that apply Electrical supply 230v 50Hz 25W Current rating 0 11A Fuse externally 3A 3 3...

Страница 11: ...having a constant separation of at least 3mm in all poles and supplying the appliance ONLY Alternatively connections may be made via a 3 pin plug and unswitched socket both complying with the requirem...

Страница 12: ...ieved by any of the three following different means a thermal evacuation of the products of combustion air mixture b mechanical evacuation of the products of combustion air mixture c natural air chang...

Страница 13: ...the outside atmosphere by a sufficient natural air change in the installation room Furthermore no provision for thermal or mechanical ventilation is required in the following particular cases building...

Страница 14: ...ed fitted to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 amp See section 3 3 f...

Страница 15: ...a first reset is not successful wait at least 15 seconds before repeating the procedure After reset an extended waiting time will occur 5 1 8 If the burner fails to ignite following a second ignition...

Страница 16: ...tra 14 Ultra 14 7 50 0mbar Ultra 21 Ultra 21 10 5 50 0mbar Ultra 28 Ultra 28 14 50 0mbar Ultra 42 Ultra 42 21 50 0mbar 5 3 2 3 In the event that the burner setting pressure is incorrect remove the cap...

Страница 17: ...mm If the electrode is badly oxidised or the ceramic insulator is cracked replace the electrode assembly see section 7 1 6 1 5 Remove any foreign matter from the flame sensor rod and check the conditi...

Страница 18: ...ition control 7 2 2 Remove the screw securing the ignition control to the Honeywell gas control valve and remove the connection cover 7 2 3 Disconnect the 10 way Molex electrical connector from the ig...

Страница 19: ...embly ceramic tiles 7 6 1 In the unlikely event that a ceramic tile is damaged and requires replacement contact Space Ray at the address shown on the front cover of this manual 7 7 Replacement Parts L...

Страница 20: ...Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual YES Is Ignition spark present at Electrodes YES Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB IE 525S...

Отзывы: