3.4.1.2 Ventilation by Mechanical Evacuation

Ventilation by mechanical evacuation is sufficient if 

10m

3

/h of exhaust air per kW of operating heat

input

 are ventilated out of the installation room.

The air/products of combustion mixture must be evacuated above the radiant heaters using fan(s).

It shall only be possible to operate the radiant heaters whilst the exhaust airflow is proven.

The maximum horizontal distance between a radiant heater and a fan shall be:

6 (six) times the fan mounting height in the case of 

wall

 openings

3 (three) times the fan mounting height in the case of 

roof

 openings

Total minimum proven ventilation airflow in 

m

3

/h 

will be:

Total installed kW input X 10 

Note:

Mechanical exhaust air openings must be positioned such that the burner stability of the
nearest appliance is unaffected.

3.4.1.3 Ventilation by Natural Air Change

Gas-fired radiant heaters may be operated without any special exhaust system if the exhaust gases
are discharged to the outside atmosphere by a sufficient natural air change in the installation room.

Furthermore, no provision for thermal or mechanical ventilation is required in the following particular
cases:

buildings with natural air change greater than 1.5 volumes per hour

buildings with a density of operating heat input not greater than 5W/m

3

 

4.

ASSEMBLY

4.1.1 

Assemble Burner Assembly to Basic Body Assembly

3.4.1.4 Air Supply

Air supply openings are required to admit air and shall be located below the radiant heaters.

The total area of the unobstructed cross-sections of all the air supply openings shall not be smaller
than the total area of the unobstructed cross-sections of all the exhaust openings.

Slits and gaps of 

fixed

 cross-section can also be used as air supply openings.

Where the air supply openings can be closed, it shall only be possible to operate the radiant heaters
when they are open.

Place the Orifice Plate (when supplied) into the venturi inlet of the Basic Body Assembly and press into position
against the shoulder. Insert the Burner Assembly spigot into the venturi inlet and align the Control Valve/Ignition
Control as shown in Fig 7:

4.1.

2

 

Page 1

1

 of 

20

Содержание Ultra 14

Страница 1: ...S Ultra 7 Ultra 7 3 5 HI LO Ultra 14 Ultra 14 7 HI LO Ultra 21 Ultra 21 10 5 HI LO Ultra 28 Ultra 28 14 HI LO Ultra 42 Ultra 42 21 HI LO Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk I...

Страница 2: ......

Страница 3: ...2 Ultra 7 14 21 28 42 12 4 3 Ultra 7 3 5 14 7 21 10 5 28 14 42 21 12 5 Commissioning 13 14 5 1 Ignition 13 5 2 Shut Down 13 5 3 Checking Gas Pressure 13 14 5 4 Flame Supervision 14 6 Servicing 15 16...

Страница 4: ...Qn 13 33 kW Hs 12 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40m...

Страница 5: ...50Hz 25W Fuse Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 5 MODEL Ultra 42 N Ultra 42 L Heat Input Qn 39 96 kW Hs 36 0 kW Hi 37 74 0 kW Hs 34 0kW Hi Appliance...

Страница 6: ...6 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40mm Electrical Sup...

Страница 7: ...use Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 10 MODEL Ultra 42 21 HI LO N Ultra 42 21 HI LO L Heat Input Qn 39 96 kW 19 98 kW Hs 37 74 kW 18 87kW Hs 36 00...

Страница 8: ...it is recommended that suitable protected welded chain 3mm x 65 links m or 6mm minimum mild steel drop rods and suitable brackets are used Attach the chains or drop rods to the 4 suspension screws of...

Страница 9: ...itted in accordance with National and Local Regulations Pipes of a smaller size than the appliance connection Rc should not be used and the pipework must be designed to achieve the nominal gas supply...

Страница 10: ...pliance must be installed in accordance with the latest or current National Regulations and any Local Regulations that apply Electrical supply 230v 50Hz 25W Current rating 0 11A Fuse externally 3A 3 3...

Страница 11: ...having a constant separation of at least 3mm in all poles and supplying the appliance ONLY Alternatively connections may be made via a 3 pin plug and unswitched socket both complying with the requirem...

Страница 12: ...ieved by any of the three following different means a thermal evacuation of the products of combustion air mixture b mechanical evacuation of the products of combustion air mixture c natural air chang...

Страница 13: ...the outside atmosphere by a sufficient natural air change in the installation room Furthermore no provision for thermal or mechanical ventilation is required in the following particular cases building...

Страница 14: ...ed fitted to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 amp See section 3 3 f...

Страница 15: ...a first reset is not successful wait at least 15 seconds before repeating the procedure After reset an extended waiting time will occur 5 1 8 If the burner fails to ignite following a second ignition...

Страница 16: ...tra 14 Ultra 14 7 50 0mbar Ultra 21 Ultra 21 10 5 50 0mbar Ultra 28 Ultra 28 14 50 0mbar Ultra 42 Ultra 42 21 50 0mbar 5 3 2 3 In the event that the burner setting pressure is incorrect remove the cap...

Страница 17: ...mm If the electrode is badly oxidised or the ceramic insulator is cracked replace the electrode assembly see section 7 1 6 1 5 Remove any foreign matter from the flame sensor rod and check the conditi...

Страница 18: ...ition control 7 2 2 Remove the screw securing the ignition control to the Honeywell gas control valve and remove the connection cover 7 2 3 Disconnect the 10 way Molex electrical connector from the ig...

Страница 19: ...embly ceramic tiles 7 6 1 In the unlikely event that a ceramic tile is damaged and requires replacement contact Space Ray at the address shown on the front cover of this manual 7 7 Replacement Parts L...

Страница 20: ...Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual YES Is Ignition spark present at Electrodes YES Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB IE 525S...

Отзывы: