Form 43343110
-4-
May 2021
4.0)
MINIMUM CLEARANCES TO COMBUSTIBLES
Install the warnings card (ordered separately) and complete the blank spaces using the clearances from
combustibles table below. See Section 25 for a printed copy of the warnings card.
Minimum clearances to combustibles shall be measured from the outer surfaces as shown in the following
diagram:
MINIMUM CLEARANCES TO COMBUSTIBLES
Model No.
Mounted Horizontally
Angle Mounted at
45º
Sides
Ceiling*
Below
Ends
45º Front 45º Rear
PCA-SS 75
22
”
10
”
60”
15
”
52
”
12”
PCA-SS 100
28
”
10
”
70
” **
15
”
58
”
12
”
PCA-SS 125
28
”
10
”
76
” **
20
”
66”
12
”
PCA-SS 150
34
”
10
”
81
” **
20
”
70
”
12
”
* Exhaust hood must be installed.
** Maximum clearance below reduces by 50% once you are 25ft. downstream from the burner box.
▲WARNING:
Certain materials or objects, when stored under the heater, will be subjected to radiant heat and
could be seriously damaged. Observe the Minimum Clearances to Combustibles listed in the manual and on the
heater at all times.
NOTE:
1. The clearances specified above must be maintained to combustibles and other materials that may be
damaged by temperatures 90ºF above ambient temperature. Clearances to combustibles are posted on the
burner box. In areas used for storage of combustible materials where they may be stacked below the heater,
NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to
maintain the required clearances from the heater to combustibles.” Space
-Ray recommends posting these signs
adjacent to the heater thermostat or other suitable location that will provide enhanced visibility.
2. The stated clearance to combustibles represents a surface temperature of 90 ºF (32 ºC) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyle siding, canvas, tri-ply, etc.) may
be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent
materials are protected from degradation.
Содержание PCA-SS 100
Страница 13: ...Form 43343110 12 May 2021 7 1 DIMENSIONS STRAIGHT CONFIGURATION 48 HANGING CENTERS...
Страница 14: ...Form 43343110 May 2021 13 7 2 HEATER ASSEMBLY JOINING OF TUBE SECTIONS...
Страница 21: ...Form 43343110 20 May 2021...
Страница 48: ...Form 43343110 May 2021 47 19 0 TROUBLESHOOTING GUIDE SINGLE STAGE N5 L5...
Страница 49: ...Form 43343110 48 May 2021 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Страница 50: ...Form 43343110 May 2021 49 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Страница 51: ...Form 43343110 50 May 2021 19 1 TROUBLESHOOTING GUIDE TWO STAGE N7 L7...
Страница 52: ...Form 43343110 May 2021 51 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...
Страница 53: ...Form 43343110 52 May 2021 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...
Страница 55: ...Form 43343110 54 May 2021 20 2 REMOVING GAS VALVE AND MANIFOLD ASSEMBLY 20 3 AIR SWITCH PRESSURE CHECK...