SSU-WP-1
WEATHERPROOF ENCLOSURE FOR
SMOKE DETECTORS
1. Remove paper backing from mounting template from
detector kit and affix to the air duct at desired
location.
2. Using the template as a guide, drill or punch (2) 1-1/4”
dia. holes in the air duct, for the sampling
tube/exhaust tube.
3. Position the SSU-WP-1 enclosure in such a way that
the holes (on the template and SSU-WP-1) are lined
up with each other.
4. Mark the (4) SSU-WP-1 air duct mounting holes. Then
drill (4) 3/32” (2.5mm) pilot holes as marked.
5. Secure SSU-WP-1 enclosure to the duct with (4) #12 x
3/4” sheet metal screws (SSU-WP-1 kit).
6. Fit the duct smoke detector into the 1-1/4” holes on
the air duct.
7. Secure the duct detector with sheet metal screws
(from detector kit) to the SSU-WP-1 enclosure.
8. Connect sampling tube/exhaust tube to the duct
detector (position the sampling tube in such a way
that air flows into the intake holes).
PRODUCT SPECIFICATIONS
USE:
SM/RW Series duct smoke detectors
System Sensor DNR duct smoke detector
CONDUIT KNOCKOUTS:
On bottom: 3 convertible 0.875”
MATERIAL:
16ga CRS white painted finish
FRONT ACCESS:
Removable Cover with two screws
HARDWARE:
Enclosure mounting screws and ground screw kit included
PROTECTION RATING:
Type 1 and Type 3R – UL 50 and CSA
Outdoor: Internal equipment protected from falling rain, etc: undamaged by ice formation
ENVIRONMENTAL:
See appropriate duct smoke detector specifications
APPROVALS:
UL: BGUZ.E257104
CUL: BGUX7.E257104
MOUNTING
SPACE AGE ELECTRONICS 1SAE.COM 800-486-1723 EC0429 REV. A
CAUTION:
DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE