6.3.3 Wiring the output cable
►
Wire the connection cable of the sonnenProtect through the
cable gland to the inside of the storage system.
►
Only pass the output cable through the gland top the
external of the main unit if the backup circuit is to be wired into
a sub-board. If the accessory is not to be immediately
connected, then leave the output cable & gland within the
internal cavity of the main unit.
►
When wiring the output cable into a backup load switch board
it is essential that the 30mA RCBO is used as the main switch
and then in series the supplied 6A MCB is used to protect all sub
load circuits against any excess draw from the backup circuitry.
Содержание SonnenProtect 1300-AU-IN-ATS