10 | Decommissioning
32 / 36
Installation instructions sonnenProtect 1300
10 Decommissioning
DANGER
Voltage in the event of a grid outage
Danger to life due to electrocution!
The plug outlet of the sonnenProtect remains live even in the event of a grid out-
age or when the main fuses are switched off.
The sonnenProtect must be switched off separately.
10.1 Switching off the plug outlet
Switch off the F1.P miniature circuit breaker.
The plug outlet of the sonnenProtect is switched off.
10.2 Disconnecting the sonnenProtect from the power supply
Before working inside the sonnenProtect, it must be completely disconnected from
the power supply:
1. Switch off the F1.P miniature circuit breaker.
2. Disconnect the storage system from the power supply.
3. Wait at least five minutes until the capacitors inside the storage system inverter
have discharged.
4. Check that the voltage is no longer active.