S-36 VLF
– USER MANUAL
17
4.3 Operating procedure
Before each measurement, select the greatest current measuring range (10 mA).
Switch on the mains switch
[Mains]
. The white signal lamp illuminates. At the same time, the yel-
low signal lamp illuminates if grounding has been carried out properly and if connection to ground ex-
ists. If the lamp does not illuminate, check all grounding connections.
On the display the start screen and. After a few seconds, the main menu appears.
In menu item „
3) Select Language
“, you can select the language to be used for menu control.
4.3.1
Testing with alternating voltage (VLF)
[Enter]
Select „
1) Test Parameters
“ in the main menu
(see above).
[Enter]
Select test method „
VLF
“.
[Enter]
Select frequency of VLF voltage (option, not in-
stalled on all devices!).
[Enter]
Select test voltage (RMS value). VLF test voltage
can be chosen between 5 to 36 kV in 0.5 kV-steps.
[Enter]
Set test time.
The maximum test time is 300 min.
METHOD OF TESTING
►1) VLF ◄
2) DC
TEST TIME:
► 60 min ◄
TEST VOLTAGE
► 36.0 kV rms ◄
TEST FREQUENCY
►1) 0.1 Hz
2) 0.05 Hz
3) 0.02 Hz
MAIN MENU
►1) Test Parameters◄
2) Operating Hours
3) Select Language