S-36 VLF
– USER MANUAL
10
2.3.2
DC testing
Suitable for:
MV-Cables with Paper-Oil-Insulation (PILC).
Requirements of CENELEC HD 621 standards for voltage test across the insulation:
Testing voltage:
see table
Testing time:
15 to 30 minutes
Requirement:
no breakdown shall occur during testing period
Cable rating U
0
/ U
3.6 / 6 kV
6 / 10 kV
8.7 / 15 kV
12 / 20 kV
DC-Test voltage
20-29 kV
34-48 kV
52-69 kV
67-96 kV
max. permissible leak-age
current (per core)*
500
µA/km
700
µA/km
700
µA/km
700
µA/km
* Practical values, not required in the standard.
DC-Polarity:
Testing voltage on conductor: negative
Cable shield on station ground: positive
2.3.3
Cable Sheath
– Testing
Suitable for:
MV-Cables with PE or PVC-Sheath (Jacket).
Requirements of CENELEC HD 620 for voltage test across cable sheath (jacket):
PVC-Sheath:
≤3 kV DC voltage
PE-Sheath:
≤5 kV DC voltage
Testing time:
10 minutes (practical value)
Requirement:
no breakdown shall occur during testing period
Limits for leakage currents*:
PVC at 3 kV:
max. 800
µA / km
PE at 5 kV:
max. 20
µA / km
* Practical values, not required in the standard.
Polarity:
Cable shield on negative potential,
Station ground on positive potential