Motorisation of Window Coverings
using Somfy Motors
Integration to BMS using Altus motors
Option 2
Busline Transmitter (Five channel)
•
Control of up to 5 groups of motors
•
Requires 240V power supply
•
Converts dry contact closure to Radio frequency
•
Dry contact impulse switching
o
Impulse contact closure of 5 seconds minimum
o
Contact between common and up or common and down to activate
motor
o
Simultaneous contact between a common up and down to create a stop
•
RS232 connection
o
Bits per Second- 1200
o
Data bits- 8
o
Parity- None
o
Stop Bits- 1
o
Flow Control - Hardware
o
Commands
U1 - Up Command Channel 1
S1 - Stop Command Channel 1
D1 - Down Command Channel 1
U2 - Up Command Channel 2
S2 - Stop Command Channel 2
D2 - Down Command Channel 2
Etc. for the next three channels.
•
One channel for each command required
•
Transmission range 30m in open space
•
Dimensions: 135 (h) x 130 (w) x 50 (d)
IMPORTANT: Do not activate more than 1 channel at a time. Activation of multiple
channels simultaneously will result in radio interference and motors will not operate.