User Manual UM0025_ASW3000-6000H-S2_EN_V02_0722 29
6.4.1 Conditions for the AC connection
Cable Requirements
The grid connection is established using three conductors (L, N,
and PE).
We recommend the following specifications for stranded copper
wire.
ASW3000H-S2/3680H-S2/4000H-S2/5000H-S2/6000H-S2
Object Description
Value
A
External diameter
10 to 16 mm
B
Conductor cross-section
4 to 6 mm²
C
Stripping length of the
insulated conductors
approx. 13 mm
D
Stripping length of the outer
sheath of AC cable
approx. 53 mm
The PE conductor must be 2mm longer than the L and N
conductors
Larger cross-sections should be used for longer cables.
Cable design
The conductor cross-section should be dimensioned to avoid
power loss in cables exceeding 1% of rated output power.