background image

The SollaTek DSP3P-80/120 

240/415V 80kVa

zone DefenDer Pro

Instruction manual

Important: This manual contains important safety instructions. 

Keep this manual handy for reference.

©Sollatek (UK) Limited 1996 All Rights Reserved. 

SOLLATEK and the SOLLATEK device are the trade marks of the Sollatek group of companies.

             

SollaTek (Uk) lTD  

UnIT 10 POyLE 14 IndUSTRIAL ESTATE, nEwLAndS dRIvE, POyLE, SLOUgh SL3 0dX, UnITEd KIngdOm 

Tel: Interna44 1753 688300    national  01753 688300  
Fax: Interna44 1753 685306   national  01753 685306   
E-mail: [email protected]   
www.sollatek.com

 

Tm

Tm

STaTUS InDICaTor

nOTE: ALL wIRES mUST BE COnnECTEd And POwER
APPLIEd 

Before

 ThE LEd wlLL ILLUmInATE. 

The dSP3P Zonedefender PRO Series of suppressors has comprehensive, solid state, continu-
ous visual status monitoring present in each unit. The gREEn indicator light will go
out in the event the suppressor capability is exceeded or if there is an internal safety
component failure. If the light goes out, call the factory for replacement instructions.

DIaGnoSTIC InDICaTIon

The dSP3P Zone defender PRO provides a patent pending diagnostic circuitry that
monitors connected power and protection status. The following is a description of
each indication.
gREEn   (On)   AC POwER is present and protection is provided.
REd  

(OFF)

gREEn   (OFF)   AC POwER is present but the Zone defender PRO needs replaced.
REd  

(On)   In addition, an audible alarm will sound and the remote indication will

 

 

change states.

gREEn   (OFF)   AC POwER or ground is missing. verify wire connections are correct.
REd 

(OFF)   make sure circuit breaker is engaged. Check panel for power.

remote Status Indication

The dSP3P Zone defender PRO provides for remote monitoring via a (normally open) or
(normally closed) circuit. The circuit is rated for 3amps at 120vAC. The common wire is
yELLOw, the normally open wire is BLUE and the normally closed wire is REd.

MaInTenanCe

At intervals not exceeding two months, check:
1. Status indication light
2. Conditions of connecting cables

noTe: no customer serviceable parts inside. opening unit WIll void Warranty.

 

Отзывы: